Series
165
Automatic Transfer Switch
for use on Standby Systems
Cat No 165A2200F3C
Ser No 123456
200 A BOM 999999
240 V 60 Hz
381333–163 B
ASCO POWER TECHNOLOGIES L.P. 50 Hanover Road, Florham Park, New Jersey 07932–1591 USA
telephone 1 800 937–2726 (ASCO), for service call 1 800 800–2726 (ASCO) www.asco.com
Series 165 Automatic Transfer Switches
rated 100 and 200 amps, single phas e, 240 V ac
Owner’s
Manual
for automatic 2–wire start generators
DANGER is used in this manual
to warn of risk of electrical shock
from high voltages capable of
causing shock, burns, or death.
WARNING is used in this
manual to warn of possible
personal injury.
!
CAUTIONisusedinthismanualtowarn
of possible equipment damage.
!
Installation should be performed by a licensed electrician
and in accordance with the National Electrical Code (NEC)
and all local electrical code requirements. Read and
understand a ll instructions before installing, s ervicing, or
operating. Failuretodosocouldresultinserious
personal injuries or property damage.
ASCO Series 165 Automatic Transfer Switches are Listed
under the Underwriter’s Laboratories Standard for Transfer
Switch Equipment, UL–1008. They are intended for use
only in optional standby systems in accordance with the
National Electrical Code, NEC/NFPA 70, Art icle 702. This
ATS is for use with 2–wire automatic start generators only.
Refer to Application Information 381339–219 to confirm
that you have selected the appropriate product for t he
intended installation.
Rating Label
Each Auto matic Transfer Switch (A TS) has rating labels to
define the lo ads and fault current withstand/ cl o sing ratings.
Refer to those label on the Transfer Switch for specific values.
INJURY or SWITCH DAMAGE
Do not exceed the rating label
values; it can cause personal in-
jury or serious switch damage.
!
Namepl ate
The Transfer Switch
nameplate includes data
for each specific ASCO
Series 165 ATS. Use the
switch only within the
limits shown on this
nameplate. A typical
Catalog Number is also
shown below with its
elements explai ned:
165 A 2 200 F 3 C
cont ro l gro up code
3 = automatic
product
designation
poles
2=2lines
ampere rating
100 or 200 amps
voltage code
F = 240 V AC
Catalog number
neutral
A=solidneutral
enclosure
C=Type1
F=Type3R
Page view 0
1 2 3 4 5 6 7 8

Summary of Contents

Page 1 - Namepl ate

Series165Automatic Transfer Switchfor use on Standby SystemsCat No 165A2200F3CSer No 123456200 A BOM 999999240 V 60 Hz381333–163 BASCO POWER TECHNOLOG

Page 2 - TABLE OF CONTENTS

2TABLE OF CONTENTSSpecifications 3...Introduction 3...Installation 4...

Page 3 - INTRODUCTION

3SPECIFICAT IONSENCLOSED AUTOMATIC TRANSFER SWITCHEnclosure SizeType 1 24” H x 14¼” W x 8” D...(610 mm H x 362 mm W x 203 mm D)Type 3R

Page 4 - INSTALLATION

4INSTALLATIONInstallation of the ASCO Series 165 automatic transferswitch must be performed by a licensed electrician. It mustbe installed according t

Page 5 - 2–VOLTAGECHECKS

5FUNCTIONAL TEST (after installation)After installing the Series 165 automatic transfer switchperform the following three–part functional test.1–MANUA

Page 6 - UTILIT Y F AILURE

6OPERATIONutility (preferred source)acceptable lighttransf er switch on generator(alternate source) lighttransfer switch on utility(preferred source)

Page 7 - MANUAL GENERATOR TESTING

source acceptable lightsload transfertest buttontransf er switch on generator(alternate source) lighttransfer switch on utility(preferred source) ligh

Page 8 - TROUBLESHOOTING

8TROUBLESHOOTINGThis troublesho oti ng guide describes some of the simplecauses of probl ems with the installati o n of the automati ctransfer switch.

Comments to this Manuals

No comments