60706-218INSTALLATION AND OPERATION MANUALOWNERS MANUALSPECIAL BUILD UNIT EQUIPPED WITH480 VOLT THREE PHASE RECEPTACLES
Page 860706-2181220-00switch be installed, remove the jumper and install anormally closed emergency stop switch between the twoterminals. When the em
Page 91220-0060706-218WARNING - POTENTIAL EQUIPMENT DAMAGETHIS DELTA CONFIGURATION HAS A WILD LEGTHAT PRODUCES 208 VOLTS LINE TO NEUTRAL ONG2. BE S
Page 1060706-2181220-005. For most installations 16-gauge wire is sufficient tohandle the control signal. On extremely long runs in-crease wire size
Page 111220-0060706-218G. UNIT STORAGECertain precautions must be taken if a Mobile DieselGenerator set is to be stored for a long period of time.The
Page 1260706-2181220-00DC ELECTRICAL SCHEMATICAC INTERFACECONNECTORTO GENERATOR
Page 131220-0060706-218DC ELECTRICAL SCHEMATIC LEGEND
Page 1460706-2181220-00GENERATOR WIRING DIAGRAMVOLTAGEREGULATORAC INTERFACECONNECTORTO DGC-2020GENERATOR WIRING
Page 151220-0060706-218VOLTAGE SELECTOR SWITCH WIRING
Page 1660706-2181220-00CIRCUIT BREAKER/FULL POWERTERMINAL BLOCK WIRING
Page 171220-0060706-218RECEPTACLE WIRING
TABLE OF CONTENTSPRODUCT SAFETY 1SPECIFICATIONS 2PREPARATIONUNPACKING 2OIL REQUIREMENTS 2FUEL REQUIREMENTS 2COOLANT REQUIREMENTS 3BATTERY CONNECTIONS
WINCO, Incorporated warrants to the original purchaser for 12 months that goods manufac-tured or supplied by it will be free from defects in workmans
Page 11220-0060706-218GUIDE TO PRODUCT SAFETYThis engine generator set has been designed and manu-factured to insure your personal safety. Improper u
Page 260706-2181220-00SPECIFICATIONSGENERATOR SPECIFICATIONSRP55KILOWATT 45 kWKILOVOLT-AMPS (.8 PF)56 kVAAMPERAGE 277/480 VOLT 3 PHASE 68 AMPS*120/240
Page 31220-0060706-218Filling the Fuel TankStandard Trailer - The standard trailer is equipped with asingle 110 gallon fuel tank. Use caution when fi
Page 460706-2181220-00ENGINE CONTROLMODULEDGC-2020DANGER – Explosive Fire Risk* Never smoke when near batteries* Do not cause a flame or spark in the
Page 51220-0060706-218the time of manufacture. Each generator protection functionhas an adjustable pickup and time delay setting. Meteredgenerator pa
Page 660706-2181220-00back up, up / down) to choose menu item andtime/date element to be changed.2) Press ‘L’ (Edit) to access change mode to enterPas
Page 71220-0060706-218C - TWO - 120 VOLT 20 AMP GROUND FAULTINTERRUPTER DUPLEXS. These duplex receptaclesare protected by 20 Amp circuit breakers mou