Winco HPS9000VE/C Specifications Page 37

  • Download
  • Add to my manuals
  • Print
  • Page
    / 46
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 36
GE Zenith’s ZTX Series Automatic Transfer Switches are
designed for residential and light commercial critical/
non-life safety applications requiring the dependability
and ease of operation found in a power contactor switch.
Ratings
40 to 400 amps (2, 3 and 4 pole)
UL 1008, CSA and IEC listed to 480 VAC 50/60Hz
Seismic Compliance to
IEEE-693-2005 and IBC-2003
Double throw, mechanically interlocked
contactor mechanism
Electrically operated, mechanically held
Designed for standby applications
GE Zenith’s ZTX switches are equipped with the MX60
control panel. This microprocessor control includes:
Undervoltage sensing (
90% pickup/80% dropout)
of Source
1 (normal)
Voltage and frequency sensing of Source
2 (emergency)
(
90% voltage/95% frequency pickup)
Time Delay Engine Start (
P) - 5 seconds
Time Delay Engine Warmup (
W) - Transfer to
Emergency (Source
2) - 20 seconds
Time Delay Utility Stabilization/Retransfer to
Utility (Source
1) (T) - 5 minutes
Time Delay Engine Cool Down (
U) - 5 minutes
All time delays are fixed (non-adjustable).
The unit is available in open type, NEMA 1 or NEMA 3R
enclosures. The MX60 control adds a user interface
and functionality, including:
Indicating
LEDs for source availability and switch position
Pushbuttons for test, exerciser set, timer bypass
and program cancel
Special status annunciation of in-phase transfer
and timer operation
Selectable
7, 14, 21 or 28 day (factory set 28 days)
generator (Source 2) with or without load exerciser timer
Diagnostic
LED indications in logical one-line conguration
Additional options include:
A3/A4 Auxiliary contacts (1 each) closed in Source 1
(normal) and Source 2 (emergency) positions
B9X
1.5 Amp/12 or 24 VDC Battery Charger
GE Digital Energy
Power Quality
ZTX
Automatic Transfer Switch
ZTX Series Residential & Light Commercial Switch
with
LED Control Panel (cover removed)
MX60 Microprocessor Control Panel
Page view 36
1 2 ... 32 33 34 35 36 37 38 39 40 41 42 ... 45 46

Comments to this Manuals

No comments