Winco DGC-2020 User Manual

Browse online or download User Manual for Equipment Winco DGC-2020. Winco DGC-2020 User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 338
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews

Summary of Contents

Page 1 - INSTRUCTION MANUAL

INSTRUCTION MANUAL FOR DIGITAL GENSET CONTROLLER DGC-2020 Publication: 9400200990 Revision: K 01/09

Page 2

viii DGC-2020 Introduction 9400200990 Rev K This page intentionally left blank.

Page 3

Figure 4-27. Programmable Functions Settings A Auto Transfer Switch Input: Select Input (None,

Page 4 - HIGHLAND IL 62249 USA

Figure 4-28. Remote LSM InputsSettings A Input Type: Voltage or Current. B Min/Max Input Voltag

Page 5 - REVISION HISTORY

Select the input typeB and amount of hysteresisC. A user-adjustable arming delayD disables analog input recognition during engine startup. When enable

Page 7

Remote Thermocouple Inputs An optional AEM-2020 (Analog Expansion Module) provides two thermocouple inputs. To make identifying the thermocouple input

Page 8

Figure 4-33. Contact Outputs Settings A Label Text: An alphanumeric character string with a ma

Page 9 - CONTENTS

BESTCOMSPlus settings for remote contact inputs (DGC-2020, Programmable Outputs, Remote Contact Outputs) are illustrated in Figure 4-35. Figure 4-35

Page 11 - TABLE OF CONTENTS

4-38 DGC-2020 BESTCOMSPlus Software 9400200990 Rev K

Page 12

9400200990 Rev K DGC-2020 BESTCOMSPlus Software 4-39 down to zero from the threshold time setting. The maintenance interval pre-alarm can be reset t

Page 13 - DESCRIPTION

9400200990 Rev K DGC-2020 General Information i SECTION 1  GENERAL INFORMATION TABLE OF CONTENTS SECTION 1  GENERAL INFORMATION ...

Page 14

4-40 DGC-2020 BESTCOMSPlus Software 9400200990 Rev K GOV Bias Output Limit GOV bias output limit settingsO consist of an enable/disable setting and

Page 15 - STYLE AND PART NUMBERS

Figure 4-38. Pre-Alarms Configuration A High Fuel Level: Enable or Disable, threshold is adjust

Page 16 - SPECIFICATIONS

4-42 DGC-2020 BESTCOMSPlus Software 9400200990 Rev K

Page 17

Note: ECU Support must be enabled on the Communications, CANbus Setup screen before this alarm can be configured. Figure 4-39. Alarms Configuration

Page 18

Figure 4-40. Sender Fail Configuration A Coolant Temp Sender Fail: None, Alarm, or Pre-Alarm, t

Page 19

The hysteresis settingD functions as an undervoltage dropout by preventing rapid switching of the pickup output. A frequency-based inhibit settingE pr

Page 20

settings. For example, if a scale factor contact input is received by the DGC-2020 and the scale factor setting is 2.000, the pickup setting will be d

Page 23

Figure 4-46. Generator Capability Curve vs. 40Q Response If reactive power is within the 40Q tripping region for the duration of the 40Q activation

Page 24

ii DGC-2020 General Information 9400200990 Rev K Underfrequency (81U) and Overfrequency (81O) ...

Page 25

4-50 DGC-2020 BESTCOMSPlus Software 9400200990 Rev K Overcurrent Protection (51-1, 51-2, 51-3) Two sets of overcurrent settings are provided for eac

Page 26

Figure 4-48. Overcurrent Protection Settings A Pickup: Adjustable from 0.9 to 7.75 Aac for 5 Aa

Page 27 - FRONT PANEL

During synchronization of the generator with the bus (Anticipatory mode only), the DGC-2020 uses the breaker closing timeJ to calculate the optimum ti

Page 29

Figure 4-50. Bus Condition Detection Settings A Dead Bus Threshold: Adjustable from 0 to 4,800

Page 30 - P0053-52

that is required to compensate for the breaker closure time by monitoring the frequency difference between the generator and the bus. BESTCOMSPlus aut

Page 31 - RUN STATISTICS

4-56 DGC-2020 BESTCOMSPlus Software 9400200990 Rev K

Page 32 - ALARMS-STATUS

droop is also the mode when the generator breaker is closed if kW load sharing is disabled. If it is desired to disable voltage droop, set the droop p

Page 33 - GENERAL SETTINGS

4-58 DGC-2020 BESTCOMSPlus Software 9400200990 Rev K

Page 34 - SYSTEM PARAMS

Expected rpm reduction in droop - (actual load/machine capacity)  (droop percentage/100)  rated speed. If the actual rpm drop does not match the exp

Page 35

9400200990 Rev K DGC-2020 General Information 1-1 SECTION 1  GENERAL INFORMATION DESCRIPTION The DGC-2020 Digital Genset Controller provides integr

Page 37 - PROGRAMMABLE INPUTS

Figure 4-55. Governor Output Settings A Output Type: Voltage or Current. B Response: Increasi

Page 38

Figure 4-57. Demand Start/Stop A Demand Start Stop Enable: Enable or Disable. B Delayed Start L

Page 39

Balanced Service Time If this mode is selected, units will seek to sort the start priority of all non-disabled networked units in ascending order of s

Page 40

BESTCOMSPlus network configuration settings (DGC-2020, Multigen Management, Network Configuration) are illustrated in Figure 4-59. Figure 4-59. Netw

Page 41

Figure 4-60. Programmable Senders Settings A Sender Points: Accepts up to 11 user-defined sende

Page 42 - BIAS CONTROL

Opening a Settings File To open a new instance of a settings file into BESTCOMSPlus, pull down the File menu and choose Open. The Open dialog box appe

Page 43

A dialog box will appear and notify you if any differences were found. The BESTCOMSPlus Settings Compare dialog box (Figure 4-62) is displayed where y

Page 44

CAUTION The order in which the components are upgraded is critical. Assuming a system of a DGC-2020 and expansion modules is in a state where the DGC-

Page 45

8. Click on the Upload button and the Proceed with Device Upload screen will appear. Select Yes or No. 9. After selecting Yes, the DGC-2020 Selection

Page 46

1-2 DGC-2020 General Information 9400200990 Rev K Contact Inputs and Output Contacts DGC-2020 controllers have one, dedicated emergency stop contact

Page 47

f. Click the Upload button and follow the instructions that appear to begin the upgrade process. g. After the upload is complete, disconnect communic

Page 48

9400200990 Rev K DGC-2020 BESTCOMSPlus Software 4-71 5. Load the new settings file into the DGC-2020. a. Disconnect communication from the DGC-202

Page 49 - DGC-2020 FUNCTION BLOCKS

4-72 DGC-2020 BESTCOMSPlus Software 9400200990 Rev K METERING EXPLORER The Metering Explorer is a convenient tool within BESTCOMSPlus used to naviga

Page 50

P0042-1509-20-06ACEBD Figure 4-66. Metering, Docking Options Table 4-2. Explanation of Call-Outs on Figure 4-66 Call-Out Symbol Explanation A Holdin

Page 51

Engine This screen provides information and metering of engine components. Refer to Figure 4-67. Figure 4-67. Metering, Engine Generator This screen

Page 52

Bias Control This screen provides Var/PF mode status and operating levels. Refer to Figure 4-70. Figure 4-70. Metering, Bias Control Run Statistics

Page 53

Figure 4-72. Metering, Status Inputs Contact Inputs This screen indicates the status of contact inputs, contact input alarms, and contact input pre-a

Page 54

Remote LSM Inputs When an optional LSM-2020 (Load Share Module) is connected, the value of the analog inputs is displayed on this screen. Voltage is d

Page 55

Remote RTD Inputs When an optional AEM-2020 (Analog Expansion Module) is connected, the status of the remote RTD inputs, remote RTD input alarms, and

Page 56

Figure 4-79. Metering, Inputs, Remote Analog Input Values The Calibrate button shown in Figure 4-79 opens the Analog Input Temperature Calibration s

Page 57 - MODES OF OPERATION

AEM-2020 (ANALOG EXPANSION MODULE) The optional AEM-2020 provides eight remote analog inputs, eight remote RTD inputs, two remote thermocouple inputs,

Page 58

Outputs Contact Outputs This screen indicates the status of contact outputs. The status is TRUE when the corresponding LED is green. Refer to Figure 4

Page 59

Figure 4-83. Metering, Outputs, Remote Contact Outputs Remote Analog Outputs When an optional AEM-2020 (Analog Expansion Module) is connected, the s

Page 60 - EVENT RECORDING

Figure 4-85. Metering, Alarms Event Log The event log provides a historical record of event occurrences detected by the DGC-2020. It is saved in nonv

Page 61 - Table 3-4. Event List

Figure 4-86. Metering, Event Log, Sorted by Date When viewed with BESTCOMSPlus, the event log can be sorted by Event ID, Description, Occurrence, Da

Page 62

Figure 4-88. Metering, ECU Data Engine Configuration This screen displays Engine Configuration. Refer to Figure 4-89. Figure 4-89. Metering, Engin

Page 63

Figure 4-90. Metering, Download DTC MTU The MTU reports operating information to the DGC-2020 through the CANbus interface when the ECU is configured

Page 64

MTU Status MTU Status is reported on this screen. The status is TRUE when the corresponding LED is red. Refer to Figure 4-93. Figure 4-93. Metering,

Page 65

Summary This screen displays a metering summary. Refer to Figure 4-95. Figure 4-95. Metering, Summary 9400200990 Rev K DGC

Page 66

Control Controls for stopping/starting the engine, controls for opening/closing breakers, and controls for opening/closing switches are accessed thro

Page 67

Generator Network Status This screen (Figure 4-98) displays the detected sequencing IDs of the LSM-2020’s on the network. This can only be accomplishe

Page 68

1-4 DGC-2020 General Information 9400200990 Rev K Part Numbers A ten-digit part number specifies the electrical characteristics and operational feat

Page 69

4-90 DGC-2020 BESTCOMSPlus Software 9400200990 Rev K This page intentionally left blank.

Page 70

9400200990 Rev K DGC-2020 BESTlogic+ Programmable Logic i SECTION 5  BESTlogic+ PROGRAMMABLE LOGIC TABLE OF CONTENTS SECTION 5  BESTlogic+ PROGRA

Page 71

ii DGC-2020 BESTlogic+ Programmable Logic 9400200990 Rev K This page intentionally left blank.

Page 72 - STARTUP AND ACTIVATION

SECTION 5  BESTlogic+ PROGRAMMABLE LOGIC INTRODUCTION BESTlogic+ Programmable Logic is a programming method used for managing the input, output, prot

Page 73

BESTlogic+ Composition There are three main groups of objects used for programming BESTlogic+. These groups are I/O, Components, and Elements. For det

Page 74 - COMMUNICATION

Name Description Symbol Status Input Auto Restart TRUE when the Automatic Restart function is active. Status Input Battery Charger Fail TRUE when th

Page 75

Name Description Symbol Status Input Front Panel Buttons TRUE while the EDIT front panel button is pressed. Status Input Front Panel Buttons TRUE wh

Page 76

Name Description Symbol Status Input Load Share Module Load Share Module Connected. TRUE when an optional LSM-2020 is connected to the DGC-2020. Sta

Page 77

Name Description Symbol Alarms Analog Expansion Module Remote Analog Inputs 1-8 TRUE when Over 1, Over 2, Under 1, Under 2, or Out of Range is config

Page 78 - MENU BARS

Name Description Symbol Hi Coolant Temp TRUE when the High Coolant Temp Alarm settings have been exceeded. Low Coolant Level TRUE when the Low Coo

Page 79 - SETTINGS EXPLORER

9400200990 Rev K DGC-2020 General Information 1-5 Contact Sensing Contact sensing inputs include 1 emergency stop input and 16 programmable inputs.

Page 80

Name Description Symbol Battery Charger Fail TRUE when the Battery Charger Fail function is configured as a Pre-Alarm and the activation delay has e

Page 81

Name Description Symbol Hi Coolant Temp TRUE when the High Coolant Temp Pre-Alarm threshold has been exceeded. High Fuel Level TRUE when the High

Page 82

Name Description Symbol Senders Coolant Temp Sender Fail TRUE when the Coolant Temp Sender Fail is configured as either a Pre-Alarm or Alarm and the

Page 83

Name Description Symbol XOR Input Output 0 0 0 0 1 1 1 0 1 1 1 0 XNOR Input Output 0 0 1 0 1 0 1 0 0 1 1 1 NOT (INVERTER) Input Output 0

Page 84

Table 5-3. Elements Group, Names and Descriptions Name Description Symbol Protection 27-1TRIP TRUE when the 27-1 undervoltage is in a TRIP condition

Page 85

Name Description Symbol Other ATS When this logic element is TRUE, and the DGC-2020 is in AUTO mode, the generator will run. This can be used in pla

Page 86

Name Description Symbol COOLDOWNREQ RUN Mode If the unit is in RUN mode when the Cool Down Request is received, the unit is forced to unload and open

Page 87

Name Description Symbol GENBRK This element is used to connect the breaker open and close output signals from the DGC-2020 to physical output contac

Page 88

Name Description Symbol MAINSBRK This element is used to connect the breaker open and close output signals from the DGC-2020 to physical output cont

Page 89

Name Description Symbol PARTOMAINS Setting this logic element to TRUE indicates to the DGC-2020 that it is paralleled to a utility. When parallele

Page 90

1-6 DGC-2020 General Information 9400200990 Rev K Programmable Relays (12) Rating: 2 Adc at 30 Vdc—make, break, and carry Terminals† Output 1: 5

Page 91 - SYSTEM PARAMETERS

Name Description Symbol STARTOUTPUT This element is used to drive the start output relay from logic when the Start Output Relay configuration is set

Page 92

CAUTION Modifying a logic scheme in BESTCOMSPlus does not automatically make that scheme active in the DGC-2020. The modified scheme must be uploaded

Page 93

Pickup and Dropout Timers A pickup timer produces a TRUE output when the elapsed time is greater than or equal to the Pickup Time setting after a FALS

Page 94

Opening a BESTlogic+ File To open a saved BESTlogic+ file, click on the Logic Library drop-down button on the BESTlogic+ Programmable Logic toolbar an

Page 95

Example 2 - AND Gate Connections Figure 5-5 illustrates a typical AND gate connection. In this example, Output 11 will become active when the Low Fuel

Page 96

9400200990 Rev K DGC-2020 Installation i SECTION 6  INSTALLATION TABLE OF CONTENTS SECTION 6  INSTALLATION ...

Page 97

ii DGC-2020 Installation 9400200990 Rev K Figure 6-16. Single-Phase A-B Connections for MTU MDEC ECU Applications...

Page 98

SECTION 6  INSTALLATION GENERAL DGC-2020 controllers are delivered in sturdy cartons to prevent shipping damage. Upon receipt of a system, check the

Page 99

Figure 6-2. Overall Dimensions 6-2 DGC-2020 Installation 9400200990 Rev K

Page 100

CONNECTIONS DGC-2020 connections are dependent on the application. Incorrect wiring may result in damage to the controller. NOTE Be sure that the DGC-

Page 101

9400200990 Rev K DGC-2020 General Information 1-7 Apparent Power Indicates total kVA and individual line kVA (4-wire, line-to-neutral or 3-wire, lin

Page 102

Table 6-2. Generator Current Sensing Terminals Terminal Description 68 (IA–) 69 (IA+) A-phase current sensing input 71 (IB–) 72 (IB+) B-phase current

Page 103

Table 6-5. Sender Input Terminals Terminal Description 8 (OIL) Oil pressure sender input 9 (FUEL) Fuel level sender input 10 (COOLANT) Coolant temp

Page 104 - PROGRAMMABLE OUTPUTS

6-6 DGC-2020 Installation 9400200990 Rev K Magnetic Pickup Input The magnetic pickup input accepts a speed signal over the range of 3 to 35 volts pe

Page 105

9400200990 Rev K DGC-2020 Installation 6-7 Table 6-9. Programmable Output Contact Terminals Terminal Description 51 (COM 1, 2, 3) Common connection

Page 106

NOTES 1.) If the DGC-2020 is providing one end of the J1939 bus, a 120  terminating resistor should be installed across terminals 48 (CANL) and 49 (

Page 107 - CONFIGURABLE PROTECTION

9400200990 Rev K DGC-2020 Installation 6-9 Dial-Out Modem DGC-2020 controllers with style number xxxxxMxxx have an internal modem with dial-in, dial

Page 108 - ALARM CONFIGURATION

3-Phase Wye Connections for Typical Applications Figure 6-6. 3-Phase Wye Connections for Typical Applications 6-10 DGC-2020 Installation 9400200990

Page 109

3-Phase Delta Connections for Typical Applications Figure 6-7. 3-Phase Delta Connections for Typical Applications 9400200990 Rev K DGC-2020 Installa

Page 110

Single-Phase A-B Connections for Typical Applications Figure 6-8. Single-Phase A-B Connections for Typical Applications 6-12 DGC-2020 Installation

Page 111

Single-Phase A-C Connections for Typical Applications Figure 6-9. Single-Phase A-C Connections for Typical Applications 9400200990 Rev K DGC-2020 In

Page 113

1-8 DGC-2020 General Information 9400200990 Rev K Maintenance Timer Maintenance timer indicates the time remaining until genset service is due. Valu

Page 114 - GENERATOR PROTECTION

6-14 DGC-2020 Installation 9400200990 Rev K Connections for Volvo Penta EDC III Applications Engines equipped with Volvo Penta EDC III controllers c

Page 115

3-Phase Wye Connections for Volvo Penta EDC III Applications Figure 6-10. 3-Phase Wye Connections for Volvo Penta EDC III Applications 9400200990 Rev

Page 116

3-Phase Delta Connections for Volvo Penta EDC III Applications Figure 6-11. 3-Phase Delta Connections for Volvo Penta EDC III Applications 6-16 DGC-

Page 117

Single-Phase A-B Connections for Volvo Penta EDC III Applications Figure 6-12. Single-Phase A-B Connections for Volvo Penta EDC III Applications 9400

Page 118

Single-Phase A-C Connections for Volvo Penta EDC III Applications Figure 6-13. Single-Phase A-C Connections for Volvo Penta EDC III Applications 6-18

Page 119

9400200990 Rev K DGC-2020 Installation 6-19 Connections for MTU MDEC ECU Applications MTU MDEC ECUs, supplied on some Detroit Diesel engines, can re

Page 120

3-Phase Wye Connections for MTU MDEC ECU Applications Figure 6-14. 3-Phase Wye Connections for MTU MDEC ECU Applications 6-20 DGC-2020 Installatio

Page 121 - BREAKER MANAGEMENT

3-Phase Delta Connections for MTU MDEC ECU Applications Figure 6-15. 3-Phase Delta Connections for MTU MDEC ECU Applications 9400200990 Rev K DGC-

Page 122

Single-Phase A-B Connections for MTU MDEC ECU Applications Figure 6-16. Single-Phase A-B Connections for MTU MDEC ECU Applications 6-22 DGC-2020 I

Page 123

Single-Phase A-C Connections for MTU MDEC ECU Applications Figure 6-17. Single-Phase A-C Connections for MTU MDEC ECU Applications 9400200990 Rev

Page 124

Logic Timers Range: 0 to 10 s Increment: 0.1 s Accuracy: 15 ms Communication Interface USB Specification Compatibility: USB 2.0 Data Transfer Spe

Page 125

Connections with AEM-2020, CEM-2020, and LSM-2020 The AEM-2020 (Analog Expansion Module), CEM-2020 (Contact Expansion Module), and LSM-2020 (Load Shar

Page 126 - BIAS CONTROL SETTINGS

9400200990 Rev K DGC-2020 Maintenance and Troubleshooting i SECTION 7  MAINTENANCE AND TROUBLESHOOTING TABLE OF CONTENTS SECTION 7  MAINTENANCE A

Page 127

ii DGC-2020 Maintenance and Troubleshooting 9400200990 Rev K This page intentionally left blank.

Page 128

SECTION 7  MAINTENANCE AND TROUBLESHOOTING MAINTENANCE Preventative maintenance consists of periodic replacement of the backup battery (optional) and

Page 129

7-2 DGC-2020 Maintenance and Troubleshooting 9400200990 Rev K Step 3. Verify that all Ethernet devices comply with IEC 61000-4 series of specifica

Page 130 - MULTIGEN MANAGEMENT

9400200990 Rev K DGC-2020 Maintenance and Troubleshooting 7-3 Step 2. Ensure that the proper current is present at the DGC-2020 current sensing in

Page 131

7-4 DGC-2020 Maintenance and Troubleshooting 9400200990 Rev K the logic output that would normally be the breaker close output. Map another virtual

Page 132

9400200990 Rev K DGC-2020 Maintenance and Troubleshooting 7-5 Synchronizer Determining if the Synchronizer is Active Step 1: Disable the speed tr

Page 133

7-6 DGC-2020 Maintenance and Troubleshooting 9400200990 Rev K If the speed still does not change when varying the bias:  Verify that the gov

Page 134 - PROGRAMMABLE SENDERS

9400200990 Rev K DGC-2020 LSM-2020 (Load Share Module) i SECTION 8  LSM-2020 (LOAD SHARE MODULE) TABLE OF CONTENTS TTSECTION 8  LSM-2020 (LOAD SH

Page 135 - FILE MANAGEMENT

CAUTION Replacement of the backup battery for the real-time clock should be performed only by qualified personnel. Do not short-circuit the battery, r

Page 136

ii DGC-2020 LSM-2020 (Load Share Module) 9400200990 Rev K Figures UUFigure 8-1. Device Info Screen...

Page 137

9400200990 Rev K DGC-2020 LSM-2020 (Load Share Module) 8-1 SECTION 8  LSM-2020 (LOAD SHARE MODULE) GENERAL INFORMATION The LSM-2020 is a remote aux

Page 138

8-2 DGC-2020 LSM-2020 (Load Share Module) 9400200990 Rev K Communication Interface CANbus Differential Bus Voltage: 1.5 to 3 Vdc Maximum Voltage:

Page 139

9400200990 Rev K DGC-2020 LSM-2020 (Load Share Module) 8-3 CE Compliance This product complies with the requirements of the following EC Directives:

Page 140

8-4 DGC-2020 LSM-2020 (Load Share Module) 9400200990 Rev K Generator Sequencing Machines can be added or removed from the power system based on load

Page 141

Figure 8-1. Device Info Screen A Application Version: When configuring Load Share Module settin

Page 142 - METERING EXPLORER

Figure 8-2. Device Security Setup Screen A Access Level/Password: Read-only value obtained when

Page 143 - 09-20-06

5.50 [139.7]151617186.38 [162.0]7.50 [190.5] 8.38 [212.8]1.39 [35.3]1234567891011121314P0052-36P2J3 Figure 8-3. LSM-2020 Overall Dimensions Connection

Page 144

8-8 DGC-2020 LSM-2020 (Load Share Module) 9400200990 Rev K Operating Power The LSM-2020 operating power input accepts either 12 Vdc or 24 Vdc and to

Page 145

CANbus Interface These terminals provide communication using the SAE J1939 protocol and provide high-speed communication between the LSM-2020 and the

Page 146

UL/CSA Approval “cURus” recognized to UL Standard 508 & CSA Standard C22.2 No. 14. CSA certified to CSA C22.2 No. 14. Part Numbers 9400200105 and

Page 147

AEM-2020(Optional)DGC-2020Other DevicesP0053-59Engine120 ohmTerminationCAN-HCAN-LCEM-2020 (Optional)LSM-2020120 ohmTerminationBusStub Figure 8-5. CANb

Page 148

DGC-2020GEN ENGINEGOVLSM-2020AVR17181415101112CANLCANHGNDAVR+AVR-GOV+GOV-504948 CANLCANHGND56LS+LS-DGC-2020GEN ENGINEGOVLSM-2020AVR17181415101112CANLC

Page 149

Connections using AVR’, GOV’, and LS’ Additional terminals provide a landing point to add series resistance to the GOV, AVR, and LS analog outputs. Th

Page 150

123456789101112131415161718EthernetLSM-2020AVR+AVR-AVR’GOV+GOV-GOV’CANLCANHGNDV+IN-I+LS+LS-LS’B-B+GNDGovernorAnalog Aux InputDGC-2020CANLCANHSHIELDP00

Page 151

8-14 DGC-2020 LSM-2020 (Load Share Module) 9400200990 Rev K This page intentionally left blank.

Page 152

9400200990 Rev K DGC-2020 CEM-2020 (Contact Expansion Module) i SECTION 9  CEM-2020 (CONTACT EXPANSION MODULE) TABLE OF CONTENTS SECTION 9  CEM-2

Page 153

ii DGC-2020 CEM-2020 (Contact Expansion Module) 9400200990 Rev K This page intentionally left blank.

Page 154

9400200990 Rev K DGC-2020 CEM-2020 (Contact Expansion Module) 9-1 SECTION 9  CEM-2020 (CONTACT EXPANSION MODULE) GENERAL INFORMATION The optional C

Page 155

9-2 DGC-2020 CEM-2020 (Contact Expansion Module) 9400200990 Rev K HALT (Highly Accelerated Life Testing) HALT is used by Basler Electric to prove th

Page 156

BESTCOMSPlus SOFTWARE BESTCOMSPlus provides the user with a point-and-click means to set and monitor the Contact Expansion Module. Installation and op

Page 157

1-12 DGC-2020 General Information 9400200990 Rev K This page intentionally left blank.

Page 158

Connections Contact Expansion Module connections are dependent on the application. Incorrect wiring may result in damage to the module. NOTE Operating

Page 159 - CONVERTING SETTINGS FILES

Figure 9-2. CEM-2020 Input Contact and Output Contact Terminals CANbus Interface These terminals provide communication using the SAE J1939 protocol

Page 160

NOTES 1.) If the CEM-2020 is providing one end of the J1939 bus, a 120  terminating resistor should be installed across terminals P1- LO (CANL) and

Page 161

9400200990 Rev K DGC-2020 AEM-2020 (Analog Expansion Module) i SECTION 10  AEM-2020 (ANALOG EXPANSION MODULE) TABLE OF CONTENTS SECTION 10  AEM-2

Page 162

ii DGC-2020 AEM-2020 (Analog Expansion Module) 9400200990 Rev K This page intentionally left blank.

Page 163 - OVERVIEW OF BESTlogic+

9400200990 Rev K DGC-2020 AEM-2020 (Analog Expansion Module) 10-1 SECTION 10  AEM-2020 (ANALOG EXPANSION MODULE) GENERAL INFORMATION The optional A

Page 164

10-2 DGC-2020 AEM-2020 (Analog Expansion Module) 9400200990 Rev K Type Tests Shock 15 G in 3 perpendicular planes Vibration Swept over the following

Page 165

9400200990 Rev K DGC-2020 AEM-2020 (Analog Expansion Module) 10-3 FUNCTIONAL DESCRIPTION A functional description of the AEM-2020’s inputs and outpu

Page 166

Mounting Analog Expansion Modules are contained in an encapsulated plastic case and may be mounted in any convenient position. The construction of a A

Page 167

is mounted permanently to the board. Connector screw terminals accept a maximum wire size of 12 AWG. Thermocouple connectors accept a maximum thermoco

Page 168

9400200990 Rev K DGC-2020 Human-Machine Interface i SECTION 2  HUMAN-MACHINE INTERFACE TABLE OF CONTENTS SECTION 2  HUMAN-MACHINE INTERFACE ...

Page 169

Table 10-2. Input and Output Terminals Connector Description P1 Operating Power and CANbus P2 RTD Inputs 1 - 8 P3 Analog Inputs 1 - 8 and Analog Ou

Page 170

Table 10-3. CANbus Interface Terminals Terminal Description P1- HI (CAN H) CAN high connection (yellow wire) P1- LO (CAN L) CAN low connection (gree

Page 171

AEM-2020DGC-2020Other DevicesP0053-63Engine120 ohmTerminationCAN-HCAN-LLSM-2020(Optional)CEM-2020(Optional)120 ohmTerminationBusStub Figure 10-6. CANb

Page 172

9400200990 Rev K DGC-2020 Time Overcurrent Characteristic Curves i APPENDIX A  TIME OVERCURRENT CHARACTERISTIC CURVES TABLE OF CONTENTS APPENDIX A

Page 173

ii DGC-2020 Time Overcurrent Characteristic Curves 9400200990 Rev K This page intentionally left blank.

Page 174

APPENDIX A  TIME OVERCURRENT CHARACTERISTIC CURVES INTRODUCTION The inverse time overcurrent characteristic curves provided by the DGC-2020 (style xx

Page 175

A-2 DGC-2020 Time Overcurrent Characteristic Curves 9400200990 Rev K Table A-1. 51 Time Characteristic Curve Constants Trip Characteristic Constants

Page 176

9400200990 Rev K DGC-2020 Time Overcurrent Characteristic Curves A-3 Table A-2. Characteristic Curve Cross-Reference Curve Curve Name Similar To S1

Page 177

A-4 DGC-2020 Time Overcurrent Characteristic Curves 9400200990 Rev K Table A-3 .Time Dial Setting Cross-Reference Electromechanical R

Page 178

Figure A-1. Time Characteristic Curve S, S1, Short Inverse (Similar to ABB CO-2) 9400200990 Rev K DGC-2020 Time Overcurrent Characteristic Curves A

Page 179

ii DGC-2020 Human-Machine Interface 9400200990 Rev K This page intentionally left blank.

Page 180 - LOGIC SCHEMES

A-6 DGC-2020 Time Overcurrent Characteristic Curves 9400200990 Rev K Figure A-2. Time Characteristic Curve S2, Short Inverse (Similar To GE IAC-55)

Page 181 - PROGRAMMING BESTlogic+

9400200990 Rev K DGC-2020 Time Overcurrent Characteristic Curves A-7 Figure A-3. Time Characteristic Curve L, L1, Long Inverse (Similar to ABB CO-5

Page 182 - P0048-03

Figure A-4. Time Characteristic Curve L2, Long Inverse (Similar To GE IAC-66) A-8 DGC-2020 Time Overcurrent Characteristic Curves 9400200990 Rev

Page 183 - BESTlogic+ EXAMPLES

Figure A-5. Time Characteristic Curve D, Definite Time (Similar To ABB CO-6) 9400200990 Rev K DGC-2020 Time Overcurrent Characteristic Curves A-9

Page 184

Figure A-6. Time Characteristic Curve M, Moderately Inverse (Similar to ABB CO-7) A-10 DGC-2020 Time Overcurrent Characteristic Curves 9400200990

Page 185 - SECTION 6  INSTALLATION

Figure A-7. Time Characteristic Curve I, I1, Inverse Time (Similar to ABB CO-8) 9400200990 Rev K DGC-2020 Time Overcurrent Characteristic Curves

Page 186

Figure A-8. Time Characteristic Curve I2, Inverse Time (Similar to GE IAC-51) A-12 DGC-2020 Time Overcurrent Characteristic Curves 9400200990 Rev

Page 187

Figure A-9. Time Characteristic Curve V, V1, Very Inverse (Similar to ABB CO-9) 9400200990 Rev K DGC-2020 Time Overcurrent Characteristic Curves

Page 188

Figure A-10. Time Characteristic Curve V2, Very Inverse (Similar to GE IAC-53) A-14 DGC-2020 Time Overcurrent Characteristic Curves 9400200990 Re

Page 189 - CONNECTIONS

Figure A-11. Time Characteristic Curve E, E1, Extremely Inverse (Similar to ABB CO-11) 9400200990 Rev K DGC-2020 Time Overcurrent Characteristic C

Page 190

SECTION 2  HUMAN-MACHINE INTERFACE INTRODUCTION This section describes the components of the DGC-2020 human-machine interface (HMI). DGC-2020 HMI com

Page 191 - P0053-93

Figure A-12. Time Characteristic Curve E2, Extremely Inverse (Similar to GE IAC-77) A-16 DGC-2020 Time Overcurrent Characteristic Curves 94002009

Page 192

Figure A-13. Time Characteristic Curve A, Standard Inverse 9400200990 Rev K DGC-2020 Time Overcurrent Characteristic Curves A-17

Page 193

Figure A-14. Time Characteristic Curve B, Very Inverse A-18 DGC-2020 Time Overcurrent Characteristic Curves 9400200990 Rev K

Page 194 - P0053-95

Figure A-15. Time Characteristic Curve C, Extremely Inverse 9400200990 Rev K DGC-2020 Time Overcurrent Characteristic Curves A-19

Page 195

Figure A-16. Time Characteristic Curve G, Long Time Inverse A-20 DGC-2020 Time Overcurrent Characteristic Curves 9400200990 Rev K

Page 196

9400200990 Rev K DGC-2020 Modbus Communication i APPENDIX B  MODBUS COMMUNICATION TABLE OF CONTENTS APPENDIX B  Modbus COMMUNICATION ...

Page 197

ii DGC-2020 Modbus Communication 9400200990 Rev K This page intentionally left blank.

Page 198

9400200990 Rev K DGC-2020 Modbus Communication B-1 APPENDIX B  MODBUS COMMUNICATION INTRODUCTION General Overview An optional feature of the DGC-

Page 199

B-2 DGC-2020 Modbus Communication 9400200990 Rev K Data Block Field The query Data block contains additional information needed by the slave to perf

Page 200

9400200990 Rev K DGC-2020 Modbus Communication B-3  Function 08, Subfunction 00 - Diagnostics: Return Query Data  Function 16 - Preset Multiple

Page 201

2-2 DGC-2020 Human-Machine Interface 9400200990 Rev K Table 2-1. Front Panel HMI Descriptions Locator Description A Liquid Crystal Display. The bac

Page 202

B-4 DGC-2020 Modbus Communication 9400200990 Rev K Preset Multiple Registers, Non-Broadcast & Broadcast Preset Multiple Registers - General QUER

Page 203

9400200990 Rev K DGC-2020 Modbus Communication B-5  There are several instances of registers that are grouped together (signified as DP or TP) to

Page 204

B-6 DGC-2020 Modbus Communication 9400200990 Rev K Long Integer Data Format (INT32) The Modbus long integer data format uses two consecutive holding

Page 205

9400200990 Rev K DGC-2020 Modbus Communication B-7 The second register contains the low-order 16 bits of double precision data, and is the actual d

Page 206

B-8 DGC-2020 Modbus Communication 9400200990 Rev K MAPPING - DGC-2020 PARAMETERS INTO MODICON ADDRESS SPACE Table Conventions Table B-3 uses the con

Page 207

9400200990 Rev K DGC-2020 Modbus Communication B-9 Table B-3. Legacy Parameter Table Holding Register Parameter Range Read/Write Supported Data For

Page 208

B-10 DGC-2020 Modbus Communication 9400200990 Rev K Holding Register Parameter Range Read/Write Supported Data Format Units 40049 Threshold 3-100

Page 209

9400200990 Rev K DGC-2020 Modbus Communication B-11 Holding Register Parameter Range Read/Write Supported Data Format Units 40082 Alarm Codes indiv

Page 210 - CEM-2020

B-12 DGC-2020 Modbus Communication 9400200990 Rev K Holding Register Parameter Range Read/Write Supported Data Format Units 40110 Phase a RMS Curre

Page 211 - TROUBLESHOOTING

9400200990 Rev K DGC-2020 Modbus Communication B-13 Holding Register Parameter Range Read/Write Supported Data Format Units 40287-97 RESERVED

Page 212

9400200990 Rev K DGC-2020 Human-Machine Interface 2-3 Permissions If communications access is active through the modem or USB, the front panel will

Page 213

B-14 DGC-2020 Modbus Communication 9400200990 Rev K Holding Register Parameter Range Read/Write Supported Data Format Units 40322 Active DTC Number

Page 214

9400200990 Rev K DGC-2020 Modbus Communication B-15 Holding Register Parameter Range Read/Write Supported Data Format Units 40354 Previous DTC Numb

Page 215

B-16 DGC-2020 Modbus Communication 9400200990 Rev K Holding Register Parameter Range Read/Write Supported Data Format Units 40372 CAN Communications

Page 216

9400200990 Rev K DGC-2020 Modbus Communication B-17 Holding Register Parameter Range Read/Write Supported Data Format Units 40388 CANbus ECU Confi

Page 217

B-18 DGC-2020 Modbus Communication 9400200990 Rev K Holding Register Parameter Range Read/Write Supported Data Format Units 40444 Coolant Level 0

Page 218

9400200990 Rev K DGC-2020 Modbus Communication B-19 Holding Register Parameter Range Read/Write Supported Data Format Units 40468 Override Speed Po

Page 219

B-20 DGC-2020 Modbus Communication 9400200990 Rev K Holding Register Parameter Range Read/Write Supported Data Format Units 40509-604 RESERVED

Page 220

9400200990 Rev K DGC-2020 Modbus Communication B-21 Holding Register Parameter Range Read/Write Supported Data Format Units 40640 Gen Protection Pr

Page 221 - GENERAL INFORMATION

B-22 DGC-2020 Modbus Communication 9400200990 Rev K Holding Register Parameter Range Read/Write Supported Data Format Units 40761 MTU Pre-alarms 0-

Page 222

9400200990 Rev K DGC-2020 Modbus Communication B-23 Register Description Type Units Scaling Factor R/W Range 42052 Mains Breaker Status Int32 N/

Page 223 - FUNCTIONAL DESCRIPTION

INTRODUCTION This instruction manual provides information about the operation and installation of the DGC-2020 Digital Genset Controller. To accomplis

Page 224 - BESTCOMSPlus SOFTWARE

Changing a Setting To change a setting, navigate to the setting you want to change and press the Edit key. If you are not already logged in, you will

Page 225

B-24 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 42328 kw Integrator Limit Plus Float

Page 226 - INSTALLATION

9400200990 Rev K DGC-2020 Modbus Communication B-25 Register Description Type Units Scaling Factor R/W Range 42768 Gen Sensing Stable Overfrequenc

Page 227 - P0052-36

B-26 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 43502 Pre-Start Contact Config Int32

Page 228

9400200990 Rev K DGC-2020 Modbus Communication B-27 Register Description Type Units Scaling Factor R/W Range 43574 Speed Signal Source Uint32 N/

Page 229 - P0053-58

B-28 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 43616 DST End Week of Month Int32 N/

Page 230 - Governor

9400200990 Rev K DGC-2020 Modbus Communication B-29 Register Description Type Units Scaling Factor R/W Range 43776 Virtual Input 1 Open Int32 N/

Page 231 - Ethernet

B-30 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 44262 1 Phase Overcurrent Curve (51-1)

Page 232

9400200990 Rev K DGC-2020 Modbus Communication B-31 Register Description Type Units Scaling Factor R/W Range 44306 Underfrequency Alarm Configurat

Page 233 - External

B-32 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 44338 3 Phase Undervoltage Activation

Page 234

9400200990 Rev K DGC-2020 Modbus Communication B-33 Register Description Type Units Scaling Factor R/W Range 44396 3 Phase Reverse Power Alarm Con

Page 235 - MODULE)

9400200990 Rev K DGC-2020 Human-Machine Interface 2-5  BUS V  BUS FREQ  SYNCHRONIZER POWER  kW A  kW B  kW C  kW TOTAL  kVA A  kVA

Page 236

B-34 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 44516 Overspeed Alarm Enable Uint32

Page 237

9400200990 Rev K DGC-2020 Modbus Communication B-35 Register Description Type Units Scaling Factor R/W Range 44578 Maintenance Interval Pre-Alarm

Page 238

B-36 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 44634 GOV Bias Output Limit Pre-alarm

Page 239 - P0056-98

9400200990 Rev K DGC-2020 Modbus Communication B-37 Register Description Type Units Scaling Factor R/W Range 44812 Alarm Metering Int32 N/A N/A

Page 240

B-38 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 44828 Local Input Metering Int32 N/A

Page 241

9400200990 Rev K DGC-2020 Modbus Communication B-39 Register Description Type Units Scaling Factor R/W Range 44858 Session Total Engine Run Hrs. I

Page 242 - P0053-61

B-40 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 44956 Local Configurable Inputs Alarm

Page 243

9400200990 Rev K DGC-2020 Modbus Communication B-41 Register Description Type Units Scaling Factor R/W Range 44966 Remote Outputs Status Bits Int3

Page 244

B-42 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 45504 Analog Input 3 Metering Value In

Page 245

9400200990 Rev K DGC-2020 Modbus Communication B-43 Register Description Type Units Scaling Factor R/W Range 45538 AEM Input Threshold Status Bits

Page 246

2-6 DGC-2020 Human-Machine Interface 9400200990 Rev K ALARMS-STATUS  ALARMS  PRE-ALARMS  MTU FAULT CODES (Visible when ECU is configured for M

Page 247

B-44 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 45544 AEM Input Threshold Alarm Bits R

Page 248 - P0056-97

9400200990 Rev K DGC-2020 Modbus Communication B-45 Register Description Type Units Scaling Factor R/W Range 45548 AEM Input Threshold Alarm Bits

Page 249

B-46 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 45554 AEM Input Threshold Pre-Alarm Bi

Page 250 - P0053-65

9400200990 Rev K DGC-2020 Modbus Communication B-47 Register Description Type Units Scaling Factor R/W Range 45562 Analog Output 2 Metering Value

Page 251 - P0053-62

B-48 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 45570 Configurable Protection Alarm Bit

Page 252 - MAINTENANCE

9400200990 Rev K DGC-2020 Modbus Communication B-49 Register Description Type Units Scaling Factor R/W Range 45576 Gen Kvar B Int32 KiloVAr N/A

Page 253 - CHARACTERISTIC CURVES

B-50 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 46018 J1939-Rated RPM Uint32 Raw ECU P

Page 254

9400200990 Rev K DGC-2020 Modbus Communication B-51 Register Description Type Units Scaling Factor R/W Range 46052 J1939-ADEC Cylinder Cutout Code

Page 255

B-52 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 46104 J1939-ADEC T Intercooler Limit Hi

Page 256

9400200990 Rev K DGC-2020 Tuning PID Settings i APPENDIX C  TUNING PID SETTINGS TABLE OF CONTENTS APPENDIX C  TUNING PID SETTINGS ...

Page 257

P0053-51SETTINGSGENERAL SETTINGSCOMMUNICATIONSSYSTEM PARAMSPROGRAMMABLE INPUTSPROGRAMMABLE OUTPUTSALARM CONFIGURATIONGENERATOR PROTECTIONBREAKER MANAG

Page 258

ii DGC-2020 Tuning PID Settings 9400200990 Rev K This page intentionally left blank.

Page 259

9400200990 Rev K DGC-2020 Tuning PID Settings C-1 APPENDIX C  TUNING PID SETTINGS INTRODUCTION The LSM-2020 (Load Share Module) and DGC-2020 utiliz

Page 260

C-2 DGC-2020 Tuning PID Settings 9400200990 Rev K TUNING PROCEDURES Voltage Controller Tuning Procedure The voltage controller is tuned prior to the

Page 261

9400200990 Rev K DGC-2020 Tuning PID Settings C-3 Var/PF Controller Tuning Procedure Once desired voltage controller performance is obtained, the Va

Page 262

C-4 DGC-2020 Tuning PID Settings 9400200990 Rev K and the speed it is trying to reach. The important thing is that the generator’s output behaves in

Page 263

9400200990 Rev K DGC-2020 Tuning PID Settings C-5 KD - Derivative Gain If the performance with KP and KI alone is satisfactory, you may stop here. O

Page 264

C-6 DGC-2020 Tuning PID Settings 9400200990 Rev K This page intentionally left blank.

Page 266

ROUTE 143, BOX 269 HIGHLAND, IL 62249 USA http://www.basler.com, [email protected] PHONE +1 618-654-2

Page 267

2-8 DGC-2020 Human-Machine Interface 9400200990 Rev K o UTC OFFSET o DST ENABLED  VIEW DATE/TIME  VERSION INFO o FIRMWARE VERSION o BOOT CODE VE

Page 268

9400200990 Rev K DGC-2020 Human-Machine Interface 2-9 o RATED FREQ o RATED RPM o COOLDWN TIME o OFF MODE COOLDN o EPS  EPS THRESHLD  LOW LINE OV

Page 269

2-10 DGC-2020 Human-Machine Interface 9400200990 Rev K o AEM SETUP  ENABLE  CANBUS ADDR (Visible when AEM-2020 is enabled.)  VERSION INFO (Visi

Page 270

9400200990 Rev K DGC-2020 Human-Machine Interface 2-11 PROGRAMMABLE INPUTS  CONFIGURABLE INPUTS o INPUT X (X = 1 to 26)  ALARM CONFIG  ACTIVATN

Page 271

2-12 DGC-2020 Human-Machine Interface 9400200990 Rev K  OVER 2  THRESHOLD  ALARM CONFIG  UNDER 1  THRESHOLD  ALARM CONFIG  UNDER 2  THRESHOL

Page 272

9400200990 Rev K DGC-2020 Human-Machine Interface 2-13 o MAINTENANCE INTERVAL  ENABLE  THRESHOLD o BATTERY OVERVOLTAGE  ENABLE  THRESHOLD o LOW

Page 273

First Printing: November 2006 Printed in USA © 2009 Basler Electric, Highland Illinois 62249 USA All Rights Reserved January 2009 CONFIDENTIAL

Page 274

NOTE The HIGH COOLANT TEMP and LOW OIL PRESSURE alarms have an ARMING DLY setting that disables the alarm for the specified time after engine startup.

Page 275

9400200990 Rev K DGC-2020 Human-Machine Interface 2-15  CURVE  ALARM CONFIG  32 REVERSE POWER o 3 / 1 PHASE SETTINGS  PICKUP  HYSTERESIS  TI

Page 276

2-16 DGC-2020 Human-Machine Interface 9400200990 Rev K o REGUL OFFSET o CLOSING ANGLE o VG>VB o TIME DELAY o FAIL DELAY BIAS CONTROL  AVR BIAS

Page 277

9400200990 Rev K DGC-2020 Human-Machine Interface 2-17  BL ALG MAX (Visible when LSM-2020 is enabled.)  BL ALG MIN (Visible when LSM-2020 is ena

Page 278

REAR PANEL All DGC-2020 terminals and connectors are located on the rear panel. Rear panel terminals and connectors are illustrated in Figure 2-4. (To

Page 279

9400200990 Rev K DGC-2020 Human-Machine Interface 2-19 Table 2-2. Rear Panel HMI Descriptions Locator Description A, D The majority of external, DG

Page 280

2-20 DGC-2020 Human-Machine Interface 9400200990 Rev K This page intentionally left blank.

Page 281 - DATA FORMATS

9400200990 Rev K DGC-2020 Functional Description i SECTION 3  FUNCTIONAL DESCRIPTION TABLE OF CONTENTS SECTION 3  FUNCTIONAL DESCRIPTION ...

Page 282

ii DGC-2020 Functional Description 9400200990 Rev K AUTO Mode (Running)...

Page 283

SECTION 3  FUNCTIONAL DESCRIPTION INTRODUCTION This section describes how the DGC-2020 functions. A detailed description of each function block is pr

Page 284

9400200990 Rev K DGC-2020 Introduction iii REVISION HISTORY The following information provides a historical summary of the changes made to this ins

Page 285

3-2 DGC-2020 Functional Description 9400200990 Rev K Zero Crossing Detection The zero crossing of A-phase to B-phase or A-phase to C-phase (user-sel

Page 286

9400200990 Rev K DGC-2020 Functional Description 3-3 Coolant temperature sender connections are made at terminals 10 and 11 (sender common). Fuel Le

Page 287

3-4 DGC-2020 Functional Description 9400200990 Rev K Connections for the programmable inputs are provided at terminals 15 (Input 16) through 30 (Inp

Page 288

9400200990 Rev K DGC-2020 Functional Description 3-5 USB The rear-panel, mini-B USB socket enables local communication with a PC running BESTCOMSPlu

Page 289

ECU Parameter Metric Units English Units Update Rate Decimal Place  SPN Total fuel used liters gallons requested 1.5 s none 250 Trip fuel liters

Page 290

9400200990 Rev K DGC-2020 Functional Description 3-7 Table 3-3. Diagnostic Information Obtained Over the CANbus Interface Parameter Transmission Rep

Page 291

3-8 DGC-2020 Functional Description 9400200990 Rev K 265, SD BANK 2 TEST 266, SD SPD DEMAND AN 267, SD SPDMTEST BNCH 269, SD LOAD PLS ANLG 270, SD

Page 292

9400200990 Rev K DGC-2020 Functional Description 3-9 input is open (emergency stop condition), the Pre-Start, Crank, and Fuel outputs open. When the

Page 293

3-10 DGC-2020 Functional Description 9400200990 Rev K Generator Exerciser The unit will start at the designated time and will run for the specified

Page 294

9400200990 Rev K DGC-2020 Functional Description 3-11 The type of response given for a local request depends on the operating mode of the DGC-2020.

Page 295

iv DGC-2020 Introduction 9400200990 Rev K BESTCOMSPlus Version and Date Change 2.03.00, 01/09  Added Export to File feature.  Added settings for

Page 296

3-12 DGC-2020 Functional Description 9400200990 Rev K Breaker close sources are:  The DGC-2020 itself when the automatic transfer (ATS) feature is

Page 297

9400200990 Rev K DGC-2020 Functional Description 3-13 Table 3-4. Event List Event String Event Description Event Type 27-1 UNDVOLT TRP A 27-1 Unde

Page 298

3-14 DGC-2020 Functional Description 9400200990 Rev K Event String Event Description Event Type ATS INPUT CLOSED ATS Input Status AUTO RESTART A

Page 299 - Bias Control Settings

9400200990 Rev K DGC-2020 Functional Description 3-15 Event String Event Description Event Type GN BKR OP FL P Generator Breaker Fail to Open Pre

Page 300 - Bus Condition Detection

3-16 DGC-2020 Functional Description 9400200990 Rev K Event String Event Description Event Type LOST ECU COMM P Loss of ECU Communication Pre-Ala

Page 301 - Senders

9400200990 Rev K DGC-2020 Functional Description 3-17 Event String Event Description Event Type RTD_IN_X_O2 A (X = 1 to 8) User Configurable Analo

Page 302

3-18 DGC-2020 Functional Description 9400200990 Rev K This page intentionally left blank.

Page 303

9400200990 Rev K DGC-2020 BESTCOMSPlus Software i SECTION 4  BESTCOMSPlus SOFTWARE TABLE OF CONTENTS TTSECTION 4  BESTCOMSPlus SOFTWARE...

Page 304 - Control

ii DGC-2020 BESTCOMSPlus Software 9400200990 Rev K Frequency Protection (81O/U) ...

Page 305 - Protection

9400200990 Rev K DGC-2020 BESTCOMSPlus Software iii Figure 4-17. ECU Setup ...

Page 306

9400200990 Rev K DGC-2020 Introduction v Firmware Package Version and Date Change 1.08.01, 01/09  Changed time dial range of 51 element fixed time

Page 307

iv DGC-2020 BESTCOMSPlus Software 9400200990 Rev K Figure 4-78. Metering, Inputs, Remote Thermocouple Inputs...

Page 308

SECTION 4  BESTCOMSPlus SOFTWARE INTRODUCTION BESTCOMSPlus is a Windows®-based, PC application that provides a user-friendly, graphical user interfac

Page 309

Table 4-1. System Requirements for BESTCOMSPlus and the .NET Framework Component Requirement Processor 400 MHz RAM 128 MB 25 MB (if .NET Framework is

Page 310

The BESTCOMSPlus splash screen is shown for a brief time. See Figure 4-3. Figure 4-3. Splash Screen The BESTCOMSPlus platform window opens. If a DG

Page 311

Click on the Activate button when you are ready to enter the activation key you received from Basler Electric. The Device Needs Activated pop-up will

Page 312 - Metering

Figure 4-7. DGC-2020 Connection USB Communication If connecting to the DGC-2020 through a USB cable, select USB via Serial RS232, USB, and enter COM

Page 313

Modem Communication If connecting to the DGC-2020 through a telephone line, select USB via Serial RS232, Modem, and enter Phone Number. To select the

Page 314

10.0.0.0 - 10.255.255.255 172.16.0.0 - 172.31.255.255 192.168.0.0 - 192.168.255.255 If the LSM-2020 is operating on an isolated network, the Sub

Page 315

Figure 4-10. Processing, Please Wait… MENU BARS The menu bars are located near the top of the BESTCOMSPlus screen (see Figure 4-1). The upper menu ba

Page 316

Help  About... View general, detailed build, and system information Lower Menu Bar (DGC-202

Page 317

vi DGC-2020 Introduction 9400200990 Rev K DGC-2020 Hardware Version and Date Change P, 01/09  Release firmware package 1.08.01 and BESTCOMSPlus 2.0

Page 318

GENERAL SETTINGS General DGC-2020 settings consist of settings controlling the HMI display and indicators. Additional general settings include style n

Page 319

Style Number When a PC operating BESTCOMSPlus is communicating with a DGC-2020, the style number of the DGC-2020 is automatically displayed on the BES

Page 320

When on-line, read-only information includes the application versionY, boot code versionZ, application buildAA, serial numberBB, application part numb

Page 321

9400200990 Rev K DGC-2020 BESTCOMSPlus Software 4-13

Page 322

 OEM Access. This password level allows access to all settings. The default, OEM-access password is OEM.  Settings Access. This password level all

Page 323

Figure 4-15. Clock Setup A UTC Offset (min): Adjustable from -1,440 to 1,440 minutes in increme

Page 324

selected, the Fuel Solenoid output will still close during cranking and genset operation to provide a separate indication that the genset is running.

Page 325

9400200990 Rev K DGC-2020 BESTCOMSPlus Software 4-17 secondary base speed is 1,800 rpm. The Accelerator Position settingC is expressed as a percenta

Page 326

Figure 4-17. ECU Setup A ECU Type: Standard, Volvo Penta, MTU MDEC, MTU ADEC, or MTU ECU7. B Sp

Page 327

9400200990 Rev K DGC-2020 BESTCOMSPlus Software 4-19  81O Trip Alarm  81U Trip Alarm  27-1 Trip Pre-Alarm  27-2 Trip Pre-Alarm  32 Trip Pr

Page 328

9400200990 Rev K DGC-2020 Introduction vii CONTENTS SECTION 1  GENERAL INFORMATION ...

Page 329

 Overspeed Alarm  Scheduled Maintenance Pre-Alarm  Switch Not in Auto  Transfer Fail Alarm  Virtual Output X Status (X = 1 to 8)  Weak Bat

Page 330

Figure 4-19. RS-485 Setup A Baud Rate: A value of 1200, 2400, 4800, or 9600 may be selected. B

Page 331

4-22 DGC-2020 BESTCOMSPlus Software 9400200990 Rev K immediately. Furthermore, if an Off Mode Cooldown is in progress and the OFF button is pressed,

Page 332 - TUNING PROCEDURES

9400200990 Rev K DGC-2020 BESTCOMSPlus Software 4-23 Single-Phase Override The DGC-2020 will switch to single-phase voltage sensingQ when a contact

Page 333

Figure 4-20. System Settings A Generator Connection: Delta, Wye, 1-Phase A-B, 1-Phase A-C, or

Page 334

Contact Expansion Module A J1939 AddressC must be entered when the optional CEM-2020 is enabledD. Select number of CEM-2020 outputsE. Analog Expansion

Page 335

Figure 4-22. Engine Crank Settings A Cranking Style: Cycle or Continuous. B Number of Crank Cy

Page 336

Exercise Timer The exercise timer is used to start the genset at a predetermined time and run for the user-defined period. The modeA defines how often

Page 337

Bus Transformer Settings Primary and secondary bus transformer ratings are used by the automatic transfer switch function, which monitors a single-pha

Page 338

Figure 4-26. Contact Inputs Settings A Alarm Configuration: None, Alarm, or Pre-Alarm. B Activ