DSE7200 / 7300 Series Operators Manual ISSUE 13
DEEP SEA ELECTRONICS
DSE7200 / 7300 Series Operators Manual
Document Number: 057-074
Author: Anthony Manton
Page view 0
1 2 3 4 5 6 ... 121 122

Summary of Contents

Page 1 - DEEP SEA ELECTRONICS

DSE7200 / 7300 Series Operators Manual ISSUE 13 DEEP SEA ELECTRONICS DSE7200 / 7300 Series Operators Manual Document Num

Page 2 - Website:

DSE7200 / 7300 Series Operators Manual 10 3 SPECIFICATIONS 3.1 PART NUMBERING 7210 - 002 - 00 This document

Page 3

DSE7200 / 7300 Series Operators Manual 100 8.7 HIGH CURRENT SHUTDOWN / ELECTRICAL TRIP ALARM The overcurrent alarm combines a simple warning trip l

Page 4 - TABLE OF CONTENTS

DSE7200 / 7300 Series Operators Manual 101 Factory settings for the IDMT Alarm when used on a brushless alternator are as follows (screen capture fro

Page 5

DSE7200 / 7300 Series Operators Manual 102 Factory setting (Time Multiplier = 36 ‘Fastest’ trip setting (Time Multiplier = 1 Slower than Factory set

Page 6

DSE7200 / 7300 Series Operators Manual 103 8.8 EARTH FAULT SHUTDOWN / ELECTRICAL TRIP ALARM When the module is suitably connected using the ‘Earth

Page 7

DSE7200 / 7300 Series Operators Manual 104 8.9 SHORT CIRCUIT ALARM If the Short Circuit alarm is enabled, the controller begins following the IDMT ‘

Page 8 - 1 BIBLIOGRAPHY

DSE7200 / 7300 Series Operators Manual 105 8.10 MAINTENANCE ALARM Depending upon module configuration one or more levels of maintenance alarm may

Page 9 - 2 INTRODUCTION

DSE7200 / 7300 Series Operators Manual 106 Example 4 Screen capture from DSE Configuration Suite Software showing the configuration holding stop bu

Page 10 - 3 SPECIFICATIONS

DSE7200 / 7300 Series Operators Manual 107 8.12 FRONT PANEL CONFIGURATION This configuration mode allows the operator limited customising of the wa

Page 11 - 3.4 TERMINAL SPECIFICATION

DSE7200 / 7300 Series Operators Manual 108 8.13 ACCESSING THE MAIN FRONT PANEL CONFIGURATION EDITOR Ensure the engine is at rest and the module is

Page 12 - 3.6.3 FREQUENCY SENSING

DSE7200 / 7300 Series Operators Manual 109 8.13.1 EDITING A PARAMETER Enter the editor as described above. Press the (left) or (right) buttons t

Page 13 - 3.7 CURRENT SENSING

DSE7200 / 7300 Series Operators Manual 11 3.3 SHORT NAMES Short name Description DSE7000, DSE7xxx All modules in the DSE7000 Series DSE7x10 All A

Page 14 - 3.8 INPUTS

DSE7200 / 7300 Series Operators Manual 110 8.13.2 ADJUSTABLE PARAMETERS Front Panel Configuration Editor = Only available on DSE7220 / DSE7320

Page 15 - 3.8.3 CHARGE FAIL INPUT

DSE7200 / 7300 Series Operators Manual 111 Front Panel Configuration Editor (continued) Section Parameter as shown on display Settings MAINS Mains Tra

Page 16 - 3.9 OUTPUTS

DSE7200 / 7300 Series Operators Manual 112 8.14 ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR The ‘running’ editor can be entered while the engine i

Page 17 - 3.10 COMMUNICATION PORTS

DSE7200 / 7300 Series Operators Manual 113 9 COMMISSIONING 9.1.1 PRE-COMMISSIONING Before the system is started, it is recommended that the follow

Page 18 - 3.11.2 USB CONNECTION

DSE7200 / 7300 Series Operators Manual 114 10 FAULT FINDING SYMPTOM POSSIBLE REMEDY Unit is inoperative Read/Write configuration does not operate

Page 19 - 3.11.3 RS232

DSE7200 / 7300 Series Operators Manual 115 SYMPTOM POSSIBLE REMEDY Incorrect reading on Engine gauges Fail to stop alarm when engine is at rest Che

Page 20

DSE7200 / 7300 Series Operators Manual 116 11 MAINTENANCE, SPARES, REPAIR AND SERVICING The DSE7000 Series controller is designed to be Fit and Forg

Page 21 - 3.11.4 RS485

DSE7200 / 7300 Series Operators Manual 117 11.1.2 DSE7300 SERIES If you require additional plugs from DSE, please contact our Sales department using

Page 22

DSE7200 / 7300 Series Operators Manual 118 11.4 EXPANSION MODULES NOTE:- Expansion modules are not compatible with the DSE7200 series controllers.

Page 23 - 3.13 SOUNDER

DSE7200 / 7300 Series Operators Manual 119 11.5 ETHERNET (LAN) CONNECTION NOTE:- DSE860 and DSE865 cannot be used with the DSE7210 or DSE7220 contr

Page 24 - 220mm x 160mm

DSE7200 / 7300 Series Operators Manual 12 3.6 GENERATOR AND MAINS VOLTAGE / FREQUENCY SENSING 3.6.1 GENERAL Measurement type True RMS conversion

Page 25 - 3.15.1 FIXING CLIPS

DSE7200 / 7300 Series Operators Manual 120 12 WARRANTY DSE provides limited warranty to the equipment purchaser at the point of sale. For full det

Page 26

This page is intentionally blank. 121

Page 27 - 3.16 APPLICABLE STANDARDS

This page is intentionally blank 122

Page 28

DSE7200 / 7300 Series Operators Manual 13 3.7 CURRENT SENSING Measurement type True RMS conversion Sample Rate 5KHz or better Harmonics Up to 10t

Page 29 - First Digit Second Digit

DSE7200 / 7300 Series Operators Manual 14 3.8 INPUTS 3.8.1 DIGITAL INPUTS Number DSE7200 6 DSE7300 8 Arrangement Contact between terminal and g

Page 30

DSE7200 / 7300 Series Operators Manual 15 3.8.2.3 FUEL LEVEL Measurement type Resistance measurement by measuring voltage across sensor with a fix

Page 31 - 4 INSTALLATION

DSE7200 / 7300 Series Operators Manual 16 3.8.4 MAGNETIC PICKUP Type Differential input Minimum voltage 0.5V RMS Max common mode voltage ±2V Maxi

Page 32 - 4.2 TERMINAL DESCRIPTION

DSE7200 / 7300 Series Operators Manual 17 3.10 COMMUNICATION PORTS USB Port USB2.0 Device for connection to PC running DSE configuration suite onl

Page 33 - 4.2.2 ANALOGUE SENSORS

DSE7200 / 7300 Series Operators Manual 18 3.11.2 USB CONNECTION The USB port is provided to give a simple means of connection between a PC and the

Page 34

DSE7200 / 7300 Series Operators Manual 19 3.11.3 RS232 The RS232 port on the controller supports the Modbus RTU protocol. The Gencomm register tabl

Page 35 - 4.2.5 MAINS VOLTAGE SENSING

DSE7200 / 7300 Series Operators Manual 2 Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND Sales Tel: +44 (0) 1723

Page 36 - (I1,I2,I3)

DSE7200 / 7300 Series Operators Manual 20 3.11.3.2 RECOMMENDED EXTERNAL MODEMS: • Wavecom Fastrak Xtrend GSM modem kit (PSU, Antenna and modem)* D

Page 37

DSE7200 / 7300 Series Operators Manual 21 3.11.4 RS485 The RS485 port on the series controller supports the Modbus RTU protocol. The DSE Gencomm reg

Page 38 - This configuration cable

DSE7200 / 7300 Series Operators Manual 22 3.12 DSENET® FOR EXPANSION MODULES DSENet® is the interconnection cable between the host controller and

Page 39 - 4.2.10 RS232 CONNECTOR

DSE7200 / 7300 Series Operators Manual 23 3.13 SOUNDER DSE7000 Series features an internal sounder to draw attention to warning, shutdown and electr

Page 40

DSE7200 / 7300 Series Operators Manual 24 3.15 DIMENSIONS AND MOUNTING DIMENSIONS 240.0mm x 181.1mm x 41.7mm (9.4” x 7.1” x 1.6”) PANEL CUTOUT 220

Page 41

DSE7200 / 7300 Series Operators Manual 25 3.15.1 FIXING CLIPS Supplied fixing clips hold the module into the panel fascia. Withdraw the fixing clip

Page 42 - 4.3.2 7220 AMF CONTROLLER

DSE7200 / 7300 Series Operators Manual 26 3.15.2 CABLE TIE FIXING POINTS Integral cable tie fixing points are included on the rear of the module’s c

Page 43

DSE7200 / 7300 Series Operators Manual 27 3.16 APPLICABLE STANDARDS BS 4884-1 This document conforms to BS4884-1 1992 Specification for presentati

Page 44 - 4.3.4 7320 AMF CONTROLLER

DSE7200 / 7300 Series Operators Manual 28 IEEE C37.2 (Standard Electrical Power System Device Function Numbers and Contact Designations) Continued

Page 45 - 4.3.5 DSENET®

DSE7200 / 7300 Series Operators Manual 29 3.16.1 ENCLOSURE CLASSIFICATIONS IP CLASSIFICATIONS 7000 series specification under BS EN 60529 Degrees

Page 46

DSE7200 / 7300 Series Operators Manual 3 Amendments since last publication Amd. No. Comments 1 Added Maintenance Alarm 2 Added manual fuel pump an

Page 47 - 4.3.7.3 FLOATING EARTH

DSE7200 / 7300 Series Operators Manual 30 3.16.2 NEMA CLASSIFICATIONS 7000 series NEMA Rating (Approximate) 12 (Front of module when module is ins

Page 48 - 4.4 ALTERNATIVE TOPOLOGIES

DSE7200 / 7300 Series Operators Manual 31 4 INSTALLATION The DSE7000 Series module is designed to be mounted on the panel fascia. For dimension and

Page 49

DSE7200 / 7300 Series Operators Manual 32 4.2 TERMINAL DESCRIPTION 4.2.1 DC SUPPLY, FUEL AND START OUTPUTS Icon PIN No DESCRIPTION CABLE SIZE N

Page 50

DSE7200 / 7300 Series Operators Manual 33 4.2.2 ANALOGUE SENSORS PIN No DESCRIPTION CABLE SIZE NOTES 15 Sensor Common Return 0.5mm² AWG 20 Re

Page 51

DSE7200 / 7300 Series Operators Manual 34 4.2.3 MAGNETIC PICKUP, CAN AND EXPANSION PIN No DESCRIPTION CABLE SIZE NOTES 22 Magnetic pickup Posi

Page 52

DSE7200 / 7300 Series Operators Manual 35 4.2.4 LOAD SWITCHING AND GENERATOR VOLTAGE SENSING PIN No DESCRIPTION CABLE SIZE NOTES 39 Output rel

Page 53

DSE7200 / 7300 Series Operators Manual 36 4.2.6 GENERATOR CURRENT TRANSFORMERS WARNING!:- Do not disconnect this plug when the CTs are carrying cu

Page 54

DSE7200 / 7300 Series Operators Manual 37 Connection of CT s1 terminal PIN No DESCRIPTION CABLE SIZE NOTES 51 CT Secondary for Gen L1 2.5mm² A

Page 55

DSE7200 / 7300 Series Operators Manual 38 4.2.7 CONFIGURABLE DIGITAL INPUTS PIN No DESCRIPTION CABLE SIZE NOTES 60 Configurable digital input

Page 56 - 4.4.9 CT LOCATION

DSE7200 / 7300 Series Operators Manual 39 4.2.9 RS485 CONNECTOR NOTE:- RS485 connector is not fitted to the 7200 series controller. PIN No NOTES A

Page 57

DSE7200 / 7300 Series Operators Manual 4 TABLE OF CONTENTS Section Page DEEP SEA ELECTRONICS ...

Page 58 - 5 DESCRIPTION OF CONTROLS

DSE7200 / 7300 Series Operators Manual 40 4.3 TYPICAL WIRING DIAGRAMS As every system has different requirements, these diagrams show only a TYPIC

Page 59

DSE7200 / 7300 Series Operators Manual 41 4.3.1 7210 AUTOSTART CONTROLLER 3 phase, 4 wire

Page 60 - Continued overleaf

DSE7200 / 7300 Series Operators Manual 42 4.3.2 7220 AMF CONTROLLER 3 phase, 4 wire

Page 61

DSE7200 / 7300 Series Operators Manual 43 4.3.3 7310 AUTOSTART CONTROLLER 3 phase, 4 wire with restricted earth fault protection NOTE:- Earthing

Page 62 - 5.3 QUICKSTART GUIDE

DSE7200 / 7300 Series Operators Manual 44 4.3.4 7320 AMF CONTROLLER 3 phase, 4 wire with restricted earth fault protection NOTE:- Earthing the neu

Page 63

DSE7200 / 7300 Series Operators Manual 45 4.3.5 DSENET® NOTE: - This feature is only available on DSE7300 Series modules DSENet® is the communicat

Page 64 - 5.4.1 STATUS

DSE7200 / 7300 Series Operators Manual 46 4.3.6 CONNECTIONS FOR DUAL MUTUAL STANDBY DUAL MUTUAL STANDBY NOTE: - This feature is available only on

Page 65 - 5.4.2 ENGINE

DSE7200 / 7300 Series Operators Manual 47 4.3.7 EARTH SYSTEMS 4.3.7.1 NEGATIVE EARTH The typical wiring diagrams located within this document are

Page 66 - 5.4.3 GENERATOR

DSE7200 / 7300 Series Operators Manual 48 4.4 ALTERNATIVE TOPOLOGIES The 7000 controller is factory configured to connect to a 3 phase, 4 wire Star

Page 67 - 5.4.5 SERIAL PORT

DSE7200 / 7300 Series Operators Manual 49 4.4.2 SINGLE PHASE WITH RESTRICTED EARTH FAULT NOTE:- Earth fault measuring not available on 7200 series

Page 68

DSE7200 / 7300 Series Operators Manual 5 4.1 USER CONNECTIONS ...

Page 69

DSE7200 / 7300 Series Operators Manual 50 4.4.3 SINGLE PHASE WITHOUT EARTH FAULT NOTE:- Mains sensing (Terminals 47-50) is not fitted to DSE7210/ D

Page 70

DSE7200 / 7300 Series Operators Manual 51 4.4.4 2 PHASE (L1 & L2) 3 WIRE WITH RESTRICTED EARTH FAULT NOTE:- Earth fault protection alarm only

Page 71 - 5.4.6 ABOUT

DSE7200 / 7300 Series Operators Manual 52 4.4.5 2 PHASE (L1 & L2) 3 WIRE WITHOUT EARTH FAULT NOTE:- Mains sensing (Terminals 47-50) is not fitt

Page 72 - 5.4.7 CAN ERROR MESSAGES

DSE7200 / 7300 Series Operators Manual 53 4.4.6 2 PHASE (L1 & L3) 3 WIRE WITH RESTRICTED EARTH FAULT NOTE:- Earth fault protection alarm only

Page 73 - 5.5 VIEWING THE EVENT LOG

DSE7200 / 7300 Series Operators Manual 54 4.4.7 2 PHASE (L1 & L3) 3 WIRE WITHOUT EARTH FAULT MEASURING NOTE:- Mains sensing (Terminals 47-50) is

Page 74

DSE7200 / 7300 Series Operators Manual 55 4.4.8 3 PHASE 4 WIRE WITH UNRESTRICTED EARTH FAULT MEASURING NOTE:- Earth fault protection alarm only ava

Page 75 - 5.7 CONTROLS

DSE7200 / 7300 Series Operators Manual 56 4.4.9 CT LOCATION NOTE:- CT Location is not applicable to the DSE7210 / DSE7310 autostart controllers. T

Page 76

DSE7200 / 7300 Series Operators Manual 57 4.5 TYPICAL ARRANGEMENT OF DSENET® A total of twenty (20) devices can be connected to the DSENet®, made

Page 77 - 6 OPERATION (STANDALONE)

DSE7200 / 7300 Series Operators Manual 58 5 DESCRIPTION OF CONTROLS The following section details the function and meaning of the various controls

Page 78 - 6.2.1 DUMMY LOAD CONTROL

DSE7200 / 7300 Series Operators Manual 59 NOTE:- “Generator on load” LED has two modes of operation depending upon th

Page 79 - 6.2.2 LOAD SHEDDING CONTROL

DSE7200 / 7300 Series Operators Manual 6 6.5 AUTOMATIC MODE ...

Page 80 - 6.4 STOP MODE

DSE7200 / 7300 Series Operators Manual 60 5.2 DSE7220 / DSE7320 AMF CONTROL MODULE Continued overleaf.Menu navigation buttons Four configu

Page 81

DSE7200 / 7300 Series Operators Manual 61 NOTE:- “Generator on load” LED has two modes of operation depending upon the configuration of th

Page 82 - 6.4.1 ECU OVERRIDE

DSE7200 / 7300 Series Operators Manual 62 5.3 QUICKSTART GUIDE This section provides a quick start guide to the module’s operation. 5.3.1 STARTIN

Page 83 - 6.5 AUTOMATIC MODE

DSE7200 / 7300 Series Operators Manual 63 5.4 VIEWING THE INSTRUMENT PAGES It is possible to scroll to display the different pages of information by

Page 84 - 6.5.4 STOPPING SEQUENCE

DSE7200 / 7300 Series Operators Manual 64 5.4.1 STATUS This is the ‘home’ page, the page that is displayed when no other page has been selected, a

Page 85 - 6.6 MANUAL MODE

DSE7200 / 7300 Series Operators Manual 65 5.4.2 ENGINE Contains instrumentation gathered about the engine itself, some of which may be obtained usi

Page 86 - 6.6.5 MANUAL SPEED CONTROL

DSE7200 / 7300 Series Operators Manual 66 5.4.3 GENERATOR Contains electrical values of the generator (alternator), measured or derived from the mo

Page 87 - 6.6.6 STOPPING SEQUENCE

DSE7200 / 7300 Series Operators Manual 67 5.4.4 MAINS (DSE7220/DSE7320 ONLY) Contains electrical values of the mains (utility) supply, measured or

Page 88 - 6.7 TEST MODE

DSE7200 / 7300 Series Operators Manual 68 Example 1 continued – Modem diagnostics NOTE:- Modem diagnostic screens are available on 7300 module versio

Page 89 - 6.7.3 ENGINE RUNNING

DSE7200 / 7300 Series Operators Manual 69 Modem Setup Sequence 1) If the Modem and DSE7000 series communicate successfully: 2) In case of comm

Page 90

DSE7200 / 7300 Series Operators Manual 7 12 WARRANTY ... 12

Page 91 - 8 PROTECTIONS

DSE7200 / 7300 Series Operators Manual 70 Example 4 - Module RS485 port configured for connection to a modbus master. DSE7300 series modules ope

Page 92 - 8.1 PROTECTIONS DISABLED

DSE7200 / 7300 Series Operators Manual 71 5.4.6 ABOUT Contains important information about the module and the firmware versions. This information m

Page 93 - 8.1.3 CAN ALARMS

DSE7200 / 7300 Series Operators Manual 72 5.4.7 CAN ERROR MESSAGES When connected to a suitable CAN engine the 7000 series controller displays alar

Page 94 - 8.2 INDICATIONS

DSE7200 / 7300 Series Operators Manual 73 5.5 VIEWING THE EVENT LOG The DSE7000 series modules maintain a log of past alarms and/or selected status

Page 95 - 8.3 WARNINGS

DSE7200 / 7300 Series Operators Manual 74 5.6 USER CONFIGURABLE INDICATORS These LEDs can be configured by the user to indicate any one of 100+ di

Page 96

DSE7200 / 7300 Series Operators Manual 75 5.7 CONTROLS Stop / Reset This button places the module into its Stop/Reset mode. This will clear any a

Page 97 - 8.5 SHUTDOWNS

DSE7200 / 7300 Series Operators Manual 76 Transfer to generator Operative in Manual Mode only ‘Normal’ breaker button control • Allows the operato

Page 98

DSE7200 / 7300 Series Operators Manual 77 6 OPERATION (STANDALONE) The following description details the sequences followed by a module containing t

Page 99 - 8.6 ELECTRICAL TRIPS

DSE7200 / 7300 Series Operators Manual 78 6.2 DUMMY LOAD / LOAD SHEDDING CONTROL NOTE:- Dummy Load / Load Shedding Control is only available on DS

Page 100 - T = t / ((IA / I

DSE7200 / 7300 Series Operators Manual 79 6.2.2 LOAD SHEDDING CONTROL The Load Shedding Control feature (if enabled) allows for a maximum of five l

Page 101

DSE7200 / 7300 Series Operators Manual 8 1 BIBLIOGRAPHY This document refers to and is referred to by the following DSE publications which can be o

Page 102

DSE7200 / 7300 Series Operators Manual 80 6.3 SMS CONTROL NOTE:- Only available in version DSE7300 version 8+ modules with a suitable GSM modem con

Page 103 - T = K x 0.14 / ((I / I

DSE7200 / 7300 Series Operators Manual 81 STOP mode is activated by pressing the button. In STOP mode, the module will remove the generator from l

Page 104

DSE7200 / 7300 Series Operators Manual 82 6.4.1 ECU OVERRIDE NOTE:- ECU Override function is only applicable when the controller is configured for

Page 105 - 8.10 MAINTENANCE ALARM

DSE7200 / 7300 Series Operators Manual 83 6.5 AUTOMATIC MODE NOTE:- If a digital input configured to panel lock is active, changing module modes

Page 106 - 8.11 SCHEDULER

DSE7200 / 7300 Series Operators Manual 84 6.5.3 ENGINE RUNNING Once the engine is running, the Warm Up timer, if selected, begins, allowing the engi

Page 107

DSE7200 / 7300 Series Operators Manual 85 6.6 MANUAL MODE NOTE:- If a digital input configured to panel lock is active, changing module modes will

Page 108

DSE7200 / 7300 Series Operators Manual 86 6.6.3 ENGINE RUNNING In manual mode, the load is not transferred to the generator unless a ‘loading reques

Page 109 - 8.13.1 EDITING A PARAMETER

DSE7200 / 7300 Series Operators Manual 87 6.6.6 STOPPING SEQUENCE In manual mode the set will continue to run until either : • The stop button i

Page 110

DSE7200 / 7300 Series Operators Manual 88 6.7 TEST MODE NOTE:- Test Mode is only applicable to DSE7220/DSE7320 controllers. NOTE:- If a digital

Page 111

DSE7200 / 7300 Series Operators Manual 89 6.7.3 ENGINE RUNNING Once the engine is running, the Warm Up timer, if selected, begins, allowing the engi

Page 112 - 8.14.1 EDITING A PARAMETER

DSE7200 / 7300 Series Operators Manual 9 2 INTRODUCTION This document does not contain operating instructions for the DSE7500 series synchronising a

Page 113 - 9 COMMISSIONING

DSE7200 / 7300 Series Operators Manual 90 7 OPERATION (DUAL MUTUAL STANDBY) NOTE:- Dual Mutual Standby is only available in DSE7210 and DSE7310 se

Page 114 - SYMPTOM POSSIBLE REMEDY

DSE7200 / 7300 Series Operators Manual 91 8 PROTECTIONS When an alarm is present, the Audible Alarm will sound and the Common alarm LED if configur

Page 115

DSE7200 / 7300 Series Operators Manual 92 8.1 PROTECTIONS DISABLED NOTE:- This feature is available in module versions 4 and above. User configur

Page 116 - 11.1.1.2 INDIVIDUAL PLUGS

DSE7200 / 7300 Series Operators Manual 93 8.1.3 CAN ALARMS NOTE:- Please refer to the engine manufacturer’s documentation for Can error message info

Page 117 - 11.1.2.2 INDIVIDUAL PLUGS

DSE7200 / 7300 Series Operators Manual 94 8.2 INDICATIONS Indications are non-critical and often status conditions. They do not appear on the LCD o

Page 118 - 11.4 EXPANSION MODULES

DSE7200 / 7300 Series Operators Manual 95 8.3 WARNINGS Warnings are non-critical alarm conditions and do not affect the operation of the generator s

Page 119

DSE7200 / 7300 Series Operators Manual 96 Display Reason PROTECTIONS DISABLED Shutdown and electrical trip alarms can be disabled by user configurat

Page 120 - 13 DISPOSAL

DSE7200 / 7300 Series Operators Manual 97 8.5 SHUTDOWNS NOTE:- Shutdown and Electrical Trip alarms can be disabled by user configuration. See the se

Page 121

DSE7200 / 7300 Series Operators Manual 98 Display Reason GENERATOR OVER FREQUENCY The generator output frequency has risen above the preset level GE

Page 122

DSE7200 / 7300 Series Operators Manual 99 8.6 ELECTRICAL TRIPS NOTE:- Shutdown and Electrical Trip alarms can be disabled by user configuration. Se