DSE7200 / 7300 Series Operators Manual ISSUE 13 DEEP SEA ELECTRONICS DSE7200 / 7300 Series Operators Manual Document Num
DSE7200 / 7300 Series Operators Manual 10 3 SPECIFICATIONS 3.1 PART NUMBERING 7210 - 002 - 00 This document
DSE7200 / 7300 Series Operators Manual 100 8.7 HIGH CURRENT SHUTDOWN / ELECTRICAL TRIP ALARM The overcurrent alarm combines a simple warning trip l
DSE7200 / 7300 Series Operators Manual 101 Factory settings for the IDMT Alarm when used on a brushless alternator are as follows (screen capture fro
DSE7200 / 7300 Series Operators Manual 102 Factory setting (Time Multiplier = 36 ‘Fastest’ trip setting (Time Multiplier = 1 Slower than Factory set
DSE7200 / 7300 Series Operators Manual 103 8.8 EARTH FAULT SHUTDOWN / ELECTRICAL TRIP ALARM When the module is suitably connected using the ‘Earth
DSE7200 / 7300 Series Operators Manual 104 8.9 SHORT CIRCUIT ALARM If the Short Circuit alarm is enabled, the controller begins following the IDMT ‘
DSE7200 / 7300 Series Operators Manual 105 8.10 MAINTENANCE ALARM Depending upon module configuration one or more levels of maintenance alarm may
DSE7200 / 7300 Series Operators Manual 106 Example 4 Screen capture from DSE Configuration Suite Software showing the configuration holding stop bu
DSE7200 / 7300 Series Operators Manual 107 8.12 FRONT PANEL CONFIGURATION This configuration mode allows the operator limited customising of the wa
DSE7200 / 7300 Series Operators Manual 108 8.13 ACCESSING THE MAIN FRONT PANEL CONFIGURATION EDITOR Ensure the engine is at rest and the module is
DSE7200 / 7300 Series Operators Manual 109 8.13.1 EDITING A PARAMETER Enter the editor as described above. Press the (left) or (right) buttons t
DSE7200 / 7300 Series Operators Manual 11 3.3 SHORT NAMES Short name Description DSE7000, DSE7xxx All modules in the DSE7000 Series DSE7x10 All A
DSE7200 / 7300 Series Operators Manual 110 8.13.2 ADJUSTABLE PARAMETERS Front Panel Configuration Editor = Only available on DSE7220 / DSE7320
DSE7200 / 7300 Series Operators Manual 111 Front Panel Configuration Editor (continued) Section Parameter as shown on display Settings MAINS Mains Tra
DSE7200 / 7300 Series Operators Manual 112 8.14 ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR The ‘running’ editor can be entered while the engine i
DSE7200 / 7300 Series Operators Manual 113 9 COMMISSIONING 9.1.1 PRE-COMMISSIONING Before the system is started, it is recommended that the follow
DSE7200 / 7300 Series Operators Manual 114 10 FAULT FINDING SYMPTOM POSSIBLE REMEDY Unit is inoperative Read/Write configuration does not operate
DSE7200 / 7300 Series Operators Manual 115 SYMPTOM POSSIBLE REMEDY Incorrect reading on Engine gauges Fail to stop alarm when engine is at rest Che
DSE7200 / 7300 Series Operators Manual 116 11 MAINTENANCE, SPARES, REPAIR AND SERVICING The DSE7000 Series controller is designed to be Fit and Forg
DSE7200 / 7300 Series Operators Manual 117 11.1.2 DSE7300 SERIES If you require additional plugs from DSE, please contact our Sales department using
DSE7200 / 7300 Series Operators Manual 118 11.4 EXPANSION MODULES NOTE:- Expansion modules are not compatible with the DSE7200 series controllers.
DSE7200 / 7300 Series Operators Manual 119 11.5 ETHERNET (LAN) CONNECTION NOTE:- DSE860 and DSE865 cannot be used with the DSE7210 or DSE7220 contr
DSE7200 / 7300 Series Operators Manual 12 3.6 GENERATOR AND MAINS VOLTAGE / FREQUENCY SENSING 3.6.1 GENERAL Measurement type True RMS conversion
DSE7200 / 7300 Series Operators Manual 120 12 WARRANTY DSE provides limited warranty to the equipment purchaser at the point of sale. For full det
This page is intentionally blank. 121
This page is intentionally blank 122
DSE7200 / 7300 Series Operators Manual 13 3.7 CURRENT SENSING Measurement type True RMS conversion Sample Rate 5KHz or better Harmonics Up to 10t
DSE7200 / 7300 Series Operators Manual 14 3.8 INPUTS 3.8.1 DIGITAL INPUTS Number DSE7200 6 DSE7300 8 Arrangement Contact between terminal and g
DSE7200 / 7300 Series Operators Manual 15 3.8.2.3 FUEL LEVEL Measurement type Resistance measurement by measuring voltage across sensor with a fix
DSE7200 / 7300 Series Operators Manual 16 3.8.4 MAGNETIC PICKUP Type Differential input Minimum voltage 0.5V RMS Max common mode voltage ±2V Maxi
DSE7200 / 7300 Series Operators Manual 17 3.10 COMMUNICATION PORTS USB Port USB2.0 Device for connection to PC running DSE configuration suite onl
DSE7200 / 7300 Series Operators Manual 18 3.11.2 USB CONNECTION The USB port is provided to give a simple means of connection between a PC and the
DSE7200 / 7300 Series Operators Manual 19 3.11.3 RS232 The RS232 port on the controller supports the Modbus RTU protocol. The Gencomm register tabl
DSE7200 / 7300 Series Operators Manual 2 Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND Sales Tel: +44 (0) 1723
DSE7200 / 7300 Series Operators Manual 20 3.11.3.2 RECOMMENDED EXTERNAL MODEMS: • Wavecom Fastrak Xtrend GSM modem kit (PSU, Antenna and modem)* D
DSE7200 / 7300 Series Operators Manual 21 3.11.4 RS485 The RS485 port on the series controller supports the Modbus RTU protocol. The DSE Gencomm reg
DSE7200 / 7300 Series Operators Manual 22 3.12 DSENET® FOR EXPANSION MODULES DSENet® is the interconnection cable between the host controller and
DSE7200 / 7300 Series Operators Manual 23 3.13 SOUNDER DSE7000 Series features an internal sounder to draw attention to warning, shutdown and electr
DSE7200 / 7300 Series Operators Manual 24 3.15 DIMENSIONS AND MOUNTING DIMENSIONS 240.0mm x 181.1mm x 41.7mm (9.4” x 7.1” x 1.6”) PANEL CUTOUT 220
DSE7200 / 7300 Series Operators Manual 25 3.15.1 FIXING CLIPS Supplied fixing clips hold the module into the panel fascia. Withdraw the fixing clip
DSE7200 / 7300 Series Operators Manual 26 3.15.2 CABLE TIE FIXING POINTS Integral cable tie fixing points are included on the rear of the module’s c
DSE7200 / 7300 Series Operators Manual 27 3.16 APPLICABLE STANDARDS BS 4884-1 This document conforms to BS4884-1 1992 Specification for presentati
DSE7200 / 7300 Series Operators Manual 28 IEEE C37.2 (Standard Electrical Power System Device Function Numbers and Contact Designations) Continued
DSE7200 / 7300 Series Operators Manual 29 3.16.1 ENCLOSURE CLASSIFICATIONS IP CLASSIFICATIONS 7000 series specification under BS EN 60529 Degrees
DSE7200 / 7300 Series Operators Manual 3 Amendments since last publication Amd. No. Comments 1 Added Maintenance Alarm 2 Added manual fuel pump an
DSE7200 / 7300 Series Operators Manual 30 3.16.2 NEMA CLASSIFICATIONS 7000 series NEMA Rating (Approximate) 12 (Front of module when module is ins
DSE7200 / 7300 Series Operators Manual 31 4 INSTALLATION The DSE7000 Series module is designed to be mounted on the panel fascia. For dimension and
DSE7200 / 7300 Series Operators Manual 32 4.2 TERMINAL DESCRIPTION 4.2.1 DC SUPPLY, FUEL AND START OUTPUTS Icon PIN No DESCRIPTION CABLE SIZE N
DSE7200 / 7300 Series Operators Manual 33 4.2.2 ANALOGUE SENSORS PIN No DESCRIPTION CABLE SIZE NOTES 15 Sensor Common Return 0.5mm² AWG 20 Re
DSE7200 / 7300 Series Operators Manual 34 4.2.3 MAGNETIC PICKUP, CAN AND EXPANSION PIN No DESCRIPTION CABLE SIZE NOTES 22 Magnetic pickup Posi
DSE7200 / 7300 Series Operators Manual 35 4.2.4 LOAD SWITCHING AND GENERATOR VOLTAGE SENSING PIN No DESCRIPTION CABLE SIZE NOTES 39 Output rel
DSE7200 / 7300 Series Operators Manual 36 4.2.6 GENERATOR CURRENT TRANSFORMERS WARNING!:- Do not disconnect this plug when the CTs are carrying cu
DSE7200 / 7300 Series Operators Manual 37 Connection of CT s1 terminal PIN No DESCRIPTION CABLE SIZE NOTES 51 CT Secondary for Gen L1 2.5mm² A
DSE7200 / 7300 Series Operators Manual 38 4.2.7 CONFIGURABLE DIGITAL INPUTS PIN No DESCRIPTION CABLE SIZE NOTES 60 Configurable digital input
DSE7200 / 7300 Series Operators Manual 39 4.2.9 RS485 CONNECTOR NOTE:- RS485 connector is not fitted to the 7200 series controller. PIN No NOTES A
DSE7200 / 7300 Series Operators Manual 4 TABLE OF CONTENTS Section Page DEEP SEA ELECTRONICS ...
DSE7200 / 7300 Series Operators Manual 40 4.3 TYPICAL WIRING DIAGRAMS As every system has different requirements, these diagrams show only a TYPIC
DSE7200 / 7300 Series Operators Manual 41 4.3.1 7210 AUTOSTART CONTROLLER 3 phase, 4 wire
DSE7200 / 7300 Series Operators Manual 42 4.3.2 7220 AMF CONTROLLER 3 phase, 4 wire
DSE7200 / 7300 Series Operators Manual 43 4.3.3 7310 AUTOSTART CONTROLLER 3 phase, 4 wire with restricted earth fault protection NOTE:- Earthing
DSE7200 / 7300 Series Operators Manual 44 4.3.4 7320 AMF CONTROLLER 3 phase, 4 wire with restricted earth fault protection NOTE:- Earthing the neu
DSE7200 / 7300 Series Operators Manual 45 4.3.5 DSENET® NOTE: - This feature is only available on DSE7300 Series modules DSENet® is the communicat
DSE7200 / 7300 Series Operators Manual 46 4.3.6 CONNECTIONS FOR DUAL MUTUAL STANDBY DUAL MUTUAL STANDBY NOTE: - This feature is available only on
DSE7200 / 7300 Series Operators Manual 47 4.3.7 EARTH SYSTEMS 4.3.7.1 NEGATIVE EARTH The typical wiring diagrams located within this document are
DSE7200 / 7300 Series Operators Manual 48 4.4 ALTERNATIVE TOPOLOGIES The 7000 controller is factory configured to connect to a 3 phase, 4 wire Star
DSE7200 / 7300 Series Operators Manual 49 4.4.2 SINGLE PHASE WITH RESTRICTED EARTH FAULT NOTE:- Earth fault measuring not available on 7200 series
DSE7200 / 7300 Series Operators Manual 5 4.1 USER CONNECTIONS ...
DSE7200 / 7300 Series Operators Manual 50 4.4.3 SINGLE PHASE WITHOUT EARTH FAULT NOTE:- Mains sensing (Terminals 47-50) is not fitted to DSE7210/ D
DSE7200 / 7300 Series Operators Manual 51 4.4.4 2 PHASE (L1 & L2) 3 WIRE WITH RESTRICTED EARTH FAULT NOTE:- Earth fault protection alarm only
DSE7200 / 7300 Series Operators Manual 52 4.4.5 2 PHASE (L1 & L2) 3 WIRE WITHOUT EARTH FAULT NOTE:- Mains sensing (Terminals 47-50) is not fitt
DSE7200 / 7300 Series Operators Manual 53 4.4.6 2 PHASE (L1 & L3) 3 WIRE WITH RESTRICTED EARTH FAULT NOTE:- Earth fault protection alarm only
DSE7200 / 7300 Series Operators Manual 54 4.4.7 2 PHASE (L1 & L3) 3 WIRE WITHOUT EARTH FAULT MEASURING NOTE:- Mains sensing (Terminals 47-50) is
DSE7200 / 7300 Series Operators Manual 55 4.4.8 3 PHASE 4 WIRE WITH UNRESTRICTED EARTH FAULT MEASURING NOTE:- Earth fault protection alarm only ava
DSE7200 / 7300 Series Operators Manual 56 4.4.9 CT LOCATION NOTE:- CT Location is not applicable to the DSE7210 / DSE7310 autostart controllers. T
DSE7200 / 7300 Series Operators Manual 57 4.5 TYPICAL ARRANGEMENT OF DSENET® A total of twenty (20) devices can be connected to the DSENet®, made
DSE7200 / 7300 Series Operators Manual 58 5 DESCRIPTION OF CONTROLS The following section details the function and meaning of the various controls
DSE7200 / 7300 Series Operators Manual 59 NOTE:- “Generator on load” LED has two modes of operation depending upon th
DSE7200 / 7300 Series Operators Manual 6 6.5 AUTOMATIC MODE ...
DSE7200 / 7300 Series Operators Manual 60 5.2 DSE7220 / DSE7320 AMF CONTROL MODULE Continued overleaf.Menu navigation buttons Four configu
DSE7200 / 7300 Series Operators Manual 61 NOTE:- “Generator on load” LED has two modes of operation depending upon the configuration of th
DSE7200 / 7300 Series Operators Manual 62 5.3 QUICKSTART GUIDE This section provides a quick start guide to the module’s operation. 5.3.1 STARTIN
DSE7200 / 7300 Series Operators Manual 63 5.4 VIEWING THE INSTRUMENT PAGES It is possible to scroll to display the different pages of information by
DSE7200 / 7300 Series Operators Manual 64 5.4.1 STATUS This is the ‘home’ page, the page that is displayed when no other page has been selected, a
DSE7200 / 7300 Series Operators Manual 65 5.4.2 ENGINE Contains instrumentation gathered about the engine itself, some of which may be obtained usi
DSE7200 / 7300 Series Operators Manual 66 5.4.3 GENERATOR Contains electrical values of the generator (alternator), measured or derived from the mo
DSE7200 / 7300 Series Operators Manual 67 5.4.4 MAINS (DSE7220/DSE7320 ONLY) Contains electrical values of the mains (utility) supply, measured or
DSE7200 / 7300 Series Operators Manual 68 Example 1 continued – Modem diagnostics NOTE:- Modem diagnostic screens are available on 7300 module versio
DSE7200 / 7300 Series Operators Manual 69 Modem Setup Sequence 1) If the Modem and DSE7000 series communicate successfully: 2) In case of comm
DSE7200 / 7300 Series Operators Manual 7 12 WARRANTY ... 12
DSE7200 / 7300 Series Operators Manual 70 Example 4 - Module RS485 port configured for connection to a modbus master. DSE7300 series modules ope
DSE7200 / 7300 Series Operators Manual 71 5.4.6 ABOUT Contains important information about the module and the firmware versions. This information m
DSE7200 / 7300 Series Operators Manual 72 5.4.7 CAN ERROR MESSAGES When connected to a suitable CAN engine the 7000 series controller displays alar
DSE7200 / 7300 Series Operators Manual 73 5.5 VIEWING THE EVENT LOG The DSE7000 series modules maintain a log of past alarms and/or selected status
DSE7200 / 7300 Series Operators Manual 74 5.6 USER CONFIGURABLE INDICATORS These LEDs can be configured by the user to indicate any one of 100+ di
DSE7200 / 7300 Series Operators Manual 75 5.7 CONTROLS Stop / Reset This button places the module into its Stop/Reset mode. This will clear any a
DSE7200 / 7300 Series Operators Manual 76 Transfer to generator Operative in Manual Mode only ‘Normal’ breaker button control • Allows the operato
DSE7200 / 7300 Series Operators Manual 77 6 OPERATION (STANDALONE) The following description details the sequences followed by a module containing t
DSE7200 / 7300 Series Operators Manual 78 6.2 DUMMY LOAD / LOAD SHEDDING CONTROL NOTE:- Dummy Load / Load Shedding Control is only available on DS
DSE7200 / 7300 Series Operators Manual 79 6.2.2 LOAD SHEDDING CONTROL The Load Shedding Control feature (if enabled) allows for a maximum of five l
DSE7200 / 7300 Series Operators Manual 8 1 BIBLIOGRAPHY This document refers to and is referred to by the following DSE publications which can be o
DSE7200 / 7300 Series Operators Manual 80 6.3 SMS CONTROL NOTE:- Only available in version DSE7300 version 8+ modules with a suitable GSM modem con
DSE7200 / 7300 Series Operators Manual 81 STOP mode is activated by pressing the button. In STOP mode, the module will remove the generator from l
DSE7200 / 7300 Series Operators Manual 82 6.4.1 ECU OVERRIDE NOTE:- ECU Override function is only applicable when the controller is configured for
DSE7200 / 7300 Series Operators Manual 83 6.5 AUTOMATIC MODE NOTE:- If a digital input configured to panel lock is active, changing module modes
DSE7200 / 7300 Series Operators Manual 84 6.5.3 ENGINE RUNNING Once the engine is running, the Warm Up timer, if selected, begins, allowing the engi
DSE7200 / 7300 Series Operators Manual 85 6.6 MANUAL MODE NOTE:- If a digital input configured to panel lock is active, changing module modes will
DSE7200 / 7300 Series Operators Manual 86 6.6.3 ENGINE RUNNING In manual mode, the load is not transferred to the generator unless a ‘loading reques
DSE7200 / 7300 Series Operators Manual 87 6.6.6 STOPPING SEQUENCE In manual mode the set will continue to run until either : • The stop button i
DSE7200 / 7300 Series Operators Manual 88 6.7 TEST MODE NOTE:- Test Mode is only applicable to DSE7220/DSE7320 controllers. NOTE:- If a digital
DSE7200 / 7300 Series Operators Manual 89 6.7.3 ENGINE RUNNING Once the engine is running, the Warm Up timer, if selected, begins, allowing the engi
DSE7200 / 7300 Series Operators Manual 9 2 INTRODUCTION This document does not contain operating instructions for the DSE7500 series synchronising a
DSE7200 / 7300 Series Operators Manual 90 7 OPERATION (DUAL MUTUAL STANDBY) NOTE:- Dual Mutual Standby is only available in DSE7210 and DSE7310 se
DSE7200 / 7300 Series Operators Manual 91 8 PROTECTIONS When an alarm is present, the Audible Alarm will sound and the Common alarm LED if configur
DSE7200 / 7300 Series Operators Manual 92 8.1 PROTECTIONS DISABLED NOTE:- This feature is available in module versions 4 and above. User configur
DSE7200 / 7300 Series Operators Manual 93 8.1.3 CAN ALARMS NOTE:- Please refer to the engine manufacturer’s documentation for Can error message info
DSE7200 / 7300 Series Operators Manual 94 8.2 INDICATIONS Indications are non-critical and often status conditions. They do not appear on the LCD o
DSE7200 / 7300 Series Operators Manual 95 8.3 WARNINGS Warnings are non-critical alarm conditions and do not affect the operation of the generator s
DSE7200 / 7300 Series Operators Manual 96 Display Reason PROTECTIONS DISABLED Shutdown and electrical trip alarms can be disabled by user configurat
DSE7200 / 7300 Series Operators Manual 97 8.5 SHUTDOWNS NOTE:- Shutdown and Electrical Trip alarms can be disabled by user configuration. See the se
DSE7200 / 7300 Series Operators Manual 98 Display Reason GENERATOR OVER FREQUENCY The generator output frequency has risen above the preset level GE
DSE7200 / 7300 Series Operators Manual 99 8.6 ELECTRICAL TRIPS NOTE:- Shutdown and Electrical Trip alarms can be disabled by user configuration. Se